Chapter 3 Hardware description
Manual VIPA System 300V
3-4
HB130E - CP - RE_343-2AH10 - Rev. 08/41
The "SET" button is required for configuring the CP in standard operation.
The button is only activated when the CPU is in the STOP mode.
If the CP is in the
configuration mode
, the CP is configured automatically
when the button is pressed. Configuration involves the following steps:
•
The CP stores the existing slave configuration, which is indicated by the
slave display, as desired configuration in the Flash-ROM.
•
The CP then changes to the
protected mode
.
If the CP is in the
protected mode
, pressing the button "SET" the CP
switches to the
configuration mode
.
LED
Color Meaning
SF red
System
fault
The LED is lit, when:
•
the CP is in the
protected mode
and an AS-i configuration error has
occurred (for example slave failed)
•
the CP detects an internal fault (e.g. Flash-ROM defective)
•
the CP cannot change to the mode requested with the "SET" button
(for example a slave exists with address 0).
RUN
green Indicates that the CP has started up correctly.
APF
red
AS-i Power Fail
This indicates that the voltage supplied to the AS-i cable by the AS-i power
supply unit is too low or there is a complete power fail.
CER
yellow Configuration error
This LED indicates whether the slave configuration detected on the AS-i
cable matches the configuration configured on the CP (LPS). If they do not
match, the CER LED is lit.
AUP green
Autoprog
available
In the
protected mode
of the CP, this indicated that automatic address
programming of a slave is possible. Automatic address programming makes
it easier to replace a defective slave on the AS-i cable.
CM yellow
Configuration
Mode
This LED indicates the mode:
on:
configuration mode
off:
protected mode
B
green Slave display: Slave of the B address area
20+
green Slave display: group of 20
10+
green Slave display: group of 10
0...9
green Slave display: Slave address of the corresponding group
"SET" button
LEDs of the CP