Configuring the infrared detector 01737
Warning: To configure the infrared sensor, all the dip switches must be OFF.
- Prepare the control panel for configuring the radio-frequency devi-
ces (see the control panel manual).
- Open the enclosure.
Dip-switches
1
ON = Maximum range equal to approximately 10 m
1
OFF = Maximum range equal to approximately 5 m
2
ON = Selector for configuring the N/C input. It permits tran
smitting two different codes to differentiate the alarm
detected by the infrared sensor from the one detected
by the contact.
2
OFF = Infrared alarm only
3
ON = N/C contact input enabled to count 6 pulses (for
roller shutter detectors)
3
OFF = Input enabled for all other types of contact (recess-
mounting magnetic ones, for instance)
4
ON = Reduced sensitivity; two detections are needed to
have an alarm signal
4
OFF = Normal sensitivity
1 2 3 4