background image

26

!

STARTING

COLLAR

STOVE

SEALANT

BEAD

1 INCH

(25.4mm)

 FIRST VENT

COMPONENT

If the installation is for a termination cap attached directly
to the fireplace, skip to the sections,

Install Firestops

and

Vent Termination

.

3/8”

(9.5mm)

B.  Installing Vent Components

After determining which set of starting collars will be used
(top or rear), follow venting instructions accordingly.

Venting Out the Rear Vent 

(See Figure 21)

Remove the installed rear seal cap from the rear starting
collars by cutting the strap at each end. Remove the insulation
inside the 5” collar. Follow the vent configuration tables
accordingly.

Remove the 5” diameter heat shield from the 5” diameter collar by
sliding it out.

WARNING: THE TOP HEAT SHIELD (INSIDE
THE FIREBOX) MUST REMAIN ATTACHED IF
THE VENT SYSTEM IS ATTACHED TO THE
REAR STARTING COLLARS. SEE FIGURE 21.

Venting Out the Top Vent

Remove the top vent collar seal cap by removing heat
shield. Remove the insulation inside

BOTH

 the 4” diameter

and 6 5/8” diameter collars. (See Figure 21).

Remove the 4” diameter heat shield from the 4” diameter
collar by sliding it out.

You have to take the glass off for positioning the logs when
the unit is finally installed in place and finished around it.
Attach vent system to the top starting collars.

!

Figure 21.

Remove two screws

holding heat shield.

Venting Out Rear

Venting Out Top

!

WARNING:  THE REAR VENT COLLAR SEAL
CAP MUST REMAIN ATTACHED TO THE REAR

VENT COLLARS IF THE VENT SYSTEM IS ATTACHED
TO THE TOP STARTING COLLARS. SEE FIGURE 21.

!

WARNING: FAILURE TO REMOVE INSULA-
TION IN THE SET OF COLLARS YOU ARE US-
ING COULD CAUSE A FIRE.

!

WARNING: YOU MUST LEAVE THE INSULA-
TION IN PLACE IN THE SET OF COLLARS
YOU ARE NOT USING.

1.  Attach the First Vent Component to the
     Starting Collars

To attach the first vent component to the starting collars
of the fireplace:

• Apply a 3/8 inch (9.5mm) bead of stove cement around

the fireplace inner vent starting collar.

• Lock the vent components into place by sliding the con-

centric pipe sections with four (4) equally spaced interi-
or beads into the fireplace collar or previously installed
component end with four (4) equally spaced indented sec-
tions.

• When the internal beads of each outer pipe line up, ro-

tate the pipe section clockwise about one-quarter (1/4)
turn. The vent pipe is now locked together.

• Slide the ceramic fiber pad over the first vent section

and place it flush to the fireplace. Continue to add vent
components.

WARNING: A 3/8 INCH (9.5 MM) BEAD OF
STOVE CEMENT MUST BE PLACED

AROUND THE FIREPLACE INNER VENT START-
ING COLLAR BEFORE ATTACHING THE FIRST
VENT COMPONENT. FAILURE TO SEAL THIS
JOINT MAY CAUSE THE FIREPLACE TO OPER-
ATE IMPROPERLY. SEE THE DIAGRAM .

    Figure 22.    Attaching the First Vent Component
                         to the Starting Collars

HEAT

SHIELD

DISCARD

INSULATION

SEAL

CAP

SEAL

CAP

HEAT

SHIELD

INSULATION,

DISCARD

BOTH

PIECES

HEAT

SHIELD

TOP VENT

COLLAR

(UNDERNEATH)

Содержание QV32

Страница 1: ...LIANCE FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home where not prohibit ed by local codes 2 This appliance is only for use with...

Страница 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Страница 3: ...nstalling Vent Components 26 C Vent Termination 28 Step 4 Positioning Leveling and Securing the Fireplace 31 Step 5 The Gas Control Systems 31 Step 6 The Gas Supply Line 32 Step 7 Gas Pressure Require...

Страница 4: ...Installers Guide have been tested to certification standards and listed by the applicable laboratories Certification MODELS QV32 QV36 LABORATORY Underwriters Laboratories TYPE Direct Vent Gas Firepla...

Страница 5: ...re to follow these instructions will void the owner s warranty and may present a fire hazard The Quadra Fire Warranty will be voided by and Aladdin Hearth Products disclaims any responsibility for the...

Страница 6: ...61mm 30 3 4 780mm 15 3 8 390mm 15 3 4 402mm 36 917mm 41 1040mm 3 1 2 90mm 8 198mm ELECTRICAL ACCESS 26 7 8 682mm 8 5 8 219mm 6 5 8 168mm 16 1 4 415mm 8 3 4 223mm 1 2 14mm 24 610mm 34 1 2 879mm HEAT SH...

Страница 7: ...mm 16 1 4 415mm 1 2 14mm 32 1 2 827mm 2 1 4 55mm 5 1 16 129mm GAS LINE ACCESS 31 790mm 36 913mm 3 1 2 90mm 8 198mm ELECTRICAL ACCESS 23 3 8 593mm 8 5 8 219mm 6 5 8 168mm 20 1 2 521mm 31 789mm HEAT SHI...

Страница 8: ...structing the Fireplace Chase A chase is a vertical box like structure built to enclose the gas fireplace and or its vent system Vertical vents that run on the outside of a building may be but are not...

Страница 9: ...raming should be constructed of 2 X 4 lumber or heavier The framing headers may rest on the fireplace stand offs The center of the framing hole is one 1 inch 25 4mm above the center of the horizontal...

Страница 10: ...2mm 11 3 4 298mm DV 48D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 8 5 8 220mm 8 1 2 216mm 6 7 16 164mm 11 1 16 281mm 6 1 2 165mm 8 1 2 216mm 5 1 16 129mm 8 5 8 220mm 35 3 4 908mm DV 12 17D 12 17 305 432mm...

Страница 11: ...nner pipe 6 5 8 inch outer pipe 120 3048mm 24 610mm 36 914mm 60 1524mm 9 1 4 6 5 8 6 1 2 6 3 8 6 1 2 9 5 8 9 5 8 6 5 8 6 3 8 8 3 4 SL 09D 12 17 SL 12 17D SL12 17D SL 24D SL 36D SL 48D 47 3 4 35 3 4 23...

Страница 12: ...D SL D SERIES COMPONENTS IN ANY VENT SYSTEM CONFIGURATION Identifying Vent Components Approved vent system components are labeled for identi fication NO OTHER VENTING SYSTEMS OR COMPO NENTS MAY BE USE...

Страница 13: ...tion in total H when using flex vent except when using the simple up and out installation see Figure 9 Figure 9 Flex Vent The flex vent must be supported with the spacing between support intervals not...

Страница 14: ...MAX 40 FT 12 2m MODEL QV36 2 5 FT 863mm 3 FT 914mm 4 FT 1 22m 6 FT 1 86m 8 FT 2 48m 16 FT 4 8m MODEL QV32 V MIN H MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 9...

Страница 15: ...2 48 m H H1 16 MAX 4 8m Figure 14 Venting with Two 90 Elbows V FT H H1 FT 1 MIN 305 mm 2 MAX 610 mm 2 MIN 610 mm 4 MAX 1 22 m 3 MIN 914 mm 6 MAX 1 86 m 4 MIN 1 22 m 8 MAX 2 48 m H H1 8 MAX 2 48 m V H...

Страница 16: ...T 914mm 4 FT 1 22m 6 FT 1 86m 8 FT 2 48m 16 FT 4 8m MODEL QV32 V MIN H H1 MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 914mm 6 FT 1 86m 4 FT 1 22m 8 FT 2 48m 5...

Страница 17: ...2m 6 FT 1 86m 8 FT 2 48m 16 FT 4 8m MODEL QV32 V MIN H MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 914mm 6 FT 1 86m 4 FT 1 22m 8 FT 2 48m 5 FT 1 52m 16 FT 4 8m...

Страница 18: ...H1 16 MAX 4 8m V H H H1 1 MIN 305 mm 2 MAX 610 mm 4 MAX 1 22m 2 MIN 610 mm 4 MAX 1 22 m 8 MAX 2 48m 3 MIN 914 mm 6 MAX 1 86 m 12 MAX 3 72m 4 MIN 1 22 m 8 MAX 2 48 m 16 MAX 4 8m V H H1 H2 40 MAX 12 4...

Страница 19: ...TING WITH THREE 3 90o ELBOWS NATURAL GAS V H V1 H1 MAX 40 FT 12 2m VENTING WITH THREE 3 90o ELBOWS PROPANE MODEL QV32 MODEL QV36 V MIN H MAX H H1 MAX H MAX H H1 MAX 90o Elbow on Top 2 5 FT 863mm 5 FT...

Страница 20: ...2 5 FT 863mm 3 FT 914mm 4 FT 1 22m 6 FT 1 86m 8 FT 2 48m 16 FT 4 8m MODEL QV32 V MIN H H1 MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 914mm 6 FT 1 86m 4 FT 1 2...

Страница 21: ...NATURAL AND PROPANE GAS V MIN H MAX 2 609mm 5 1 52m V1 MIN H1 MAX V2 MIN 5 1 52m 5 1 52m 4 5 1 37m V V1 V2 H H1 MAX 40 12 2m V H V2 V1 H1 NOTE There MUST be a 25 reduction in total H when using flex...

Страница 22: ...Out Top WARNING THE REAR VENT COLLAR SEAL CAP MUST REMAIN ATTACHED TO THE REAR VENTCOLLARSIFTHEVENTSYSTEMISATTACHED TO THE TOP STARTING COLLARS SEE FIGURE 21 WARNING FAILURE TO REMOVE INSULA TION IN T...

Страница 23: ...ther interior or exterior walls Cut a 12 x 12 305mm x 305mm hole through the wall for D series or a 10 x 10 254mm x 254mm hole for SL D series pipe The center of the framing hole is one 1 inch 25 4mm...

Страница 24: ...9 Attic Firestop JOIST CEILING FIRESTOP CEILING NAILS 4 REQUIRED CEILING CEILING FIRESTOP RAFTER NAILS 4 REQUIRED CEILING NEW FRAMING MEMBERS EXISTING CEILING JOISTS CHIMNEY HOLE 11 280 mm or 10 254 m...

Страница 25: ...RONGLY RECOMMENDED WHENEVER POSSIBLE TO USE THE VINYL PROTECTOR KIT 30 minimum for vinyl clad soffits a vent shall not terminate directly above a sidewalk or paved driveway which is located between tw...

Страница 26: ...MUM HEIGHTS PROVID ED THE TERMINATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICAL WALL AND 2 FEET BELOW A HORIZONTAL OVERHANG NOTE This also pertains to vertical vent systems in stalled on the outside...

Страница 27: ...oning Leveling and Securing of a Fireplace Figure 34 Gas Control System STANDING PILOT Step 5 The Gas Control Systems WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL The gas control system used with...

Страница 28: ...diameter and it does not penetrate the actual firebox Open the fireplace lower grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attaching the pipe...

Страница 29: ...installed Wall Switch Position the wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch p...

Страница 30: ...DE SEAL JOINT 0 1 4 FINISH MATERIAL MAY BE COMBUSTIBLE TOP AND SIDES OF UNIT Optional Accessories Optional fan and remote control kits require that 110 120 VAC be wired to the fireplace junction box W...

Страница 31: ...ANSI Z97 1 1984 and CPSC 16 CFR 1202 Safety Glazing Certification Council SGCC 1595 and 1597 Architec tural Testing Inc Reports 02 31919 01 and 02 31917 01 This statement is in compliance with CPSC 16...

Страница 32: ...r If it is necessary to access the pilot remove the trim door and glass door THERMOCOUPLE PILOT THERMOPILE 5 To put the control in the PILOT position turn the control knob counter clockwise to the PIL...

Страница 33: ...the gas supply lines When first lighting the fireplace it will take a few minutes for the lines to purge themselves of this air Once the purging is complete the fireplace will light and will operate...

Страница 34: ...urrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check of your fireplace s flame patterns Make sure the fla...

Страница 35: ...the pilot and hold the valve knob in If the millivolt reading is less than 15mV replace the thermocouple b Defective valve If the thermocouple is producing more than 15 millivolts replace faulty valve...

Страница 36: ...downwards lope is 1 4 inch d Glass too loose and air tight packet leaks in corners after usage Tighten the corner e Bad thermopile or thermocouple Replace if necessary f Improper vent cap installation...

Страница 37: ...ning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items and installation of upgraded component parts do not quality for a...

Отзывы: