2

These units 

MUST

use one of the vent systems

described in the Installing the Fireplace section of the

Installers Guide

.

NO OTHER 

vent systems or

components

MAY BE USED.

This gas fireplace and vent assembly 

MUST

be

vented directly to the outside and 

MUST NEVER 

be

attached to a chimney serving a separate solid fuel
burning appliance. Each gas appliance 

MUST USE

a separate vent system. Common vent systems are

PROHIBITED

.

INSPECT

the external vent cap on a regular basis to

make sure that no debris is interfering with the air
flow.

The glass door assembly 

MUST

be in place and

sealed, and the trim door assembly 

MUST

be in

place on the fireplace before the unit can be placed
into safe operation.

DO NOT OPERATE 

this appliance with the glass

door removed, cracked, or broken. Replacement of
the glass door should be performed by a licensed or
qualified service person. 

DO NOT 

strike or slam the

glass door.

The glass door assembly 

SHALL ONLY 

be replaced

as a complete unit, as supplied by the gas fireplace
manufacturer.

NO SUBSTITUTE 

material may be

used.

DO NOT USE 

abrasive cleaners on the glass door

assembly.

DO NOT ATTEMPT 

to clean the glass

door when it is hot.

Turn off the gas before servicing this appliance. It is
recommended that a qualified service technician
perform an appliance check-up at the beginning of
each heating season.

Any safety screen or guard removed for servicing
must be replaced before operating this appliance.

DO NOT 

place furniture or any other combustible

household objects within 36 inches of the fireplace
front.

READ

and

UNDERSTAND

all instructions carefully

before starting the installation. 

FAILURE TO

FOLLOW

these installation instructions may result in

a possible fire hazard and will void the warranty.

Prior to the first firing of the fireplace, 

READ

the

Using Your Fireplace section of the 

Owners Guide

.

DO NOT USE 

this appliance if any part has been

under water. Immediately 

CALL

a qualified service

technician to inspect the unit and to replace any part
of the control system and any gas control which has
been under water.

THIS UNIT IS NOT FOR USE WITH SOLID FUEL.

Installation and repair should be 

PERFORMED

by a

qualified service person. The appliance and venting
system should be 

INSPECTED

before initial use and

at least annually by a professional service person.
More frequent cleaning may be required due to
excessive lint from carpeting, bedding material, etc.
It is 

IMPERATIVE

that the unit’s control

compartment, burners, and circulating air
passageways

BE KEPT CLEAN 

to provide for

adequate combustion and ventilation air.

Always

KEEP

the appliance clear and free from

combustible materials, gasoline, and other
flammable vapors and liquids.

NEVER OBSTRUCT 

the flow of combustion and

ventilation air. Keep the front of the appliance

CLEAR

of all obstacles and materials for servicing

and proper operations.

Due to the high temperature, the appliance should
be

LOCATED

out of traffic areas and away from

furniture and draperies. Clothing or flammable
material

SHOULD NOT BE PLACED 

on or near the

appliance.

Children and adults should be 

ALERTED

to the

hazards of high surface temperature and should

STAY AWAY 

to avoid burns or clothing ignition.

Young children should be 

CAREFULLY

SUPERVISED

when they are in the same room as

the appliance.

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

SAFETY AND WARNING INFORMATION

!

!

Содержание QV32

Страница 1: ...LIANCE FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home where not prohibit ed by local codes 2 This appliance is only for use with...

Страница 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Страница 3: ...nstalling Vent Components 26 C Vent Termination 28 Step 4 Positioning Leveling and Securing the Fireplace 31 Step 5 The Gas Control Systems 31 Step 6 The Gas Supply Line 32 Step 7 Gas Pressure Require...

Страница 4: ...Installers Guide have been tested to certification standards and listed by the applicable laboratories Certification MODELS QV32 QV36 LABORATORY Underwriters Laboratories TYPE Direct Vent Gas Firepla...

Страница 5: ...re to follow these instructions will void the owner s warranty and may present a fire hazard The Quadra Fire Warranty will be voided by and Aladdin Hearth Products disclaims any responsibility for the...

Страница 6: ...61mm 30 3 4 780mm 15 3 8 390mm 15 3 4 402mm 36 917mm 41 1040mm 3 1 2 90mm 8 198mm ELECTRICAL ACCESS 26 7 8 682mm 8 5 8 219mm 6 5 8 168mm 16 1 4 415mm 8 3 4 223mm 1 2 14mm 24 610mm 34 1 2 879mm HEAT SH...

Страница 7: ...mm 16 1 4 415mm 1 2 14mm 32 1 2 827mm 2 1 4 55mm 5 1 16 129mm GAS LINE ACCESS 31 790mm 36 913mm 3 1 2 90mm 8 198mm ELECTRICAL ACCESS 23 3 8 593mm 8 5 8 219mm 6 5 8 168mm 20 1 2 521mm 31 789mm HEAT SHI...

Страница 8: ...structing the Fireplace Chase A chase is a vertical box like structure built to enclose the gas fireplace and or its vent system Vertical vents that run on the outside of a building may be but are not...

Страница 9: ...raming should be constructed of 2 X 4 lumber or heavier The framing headers may rest on the fireplace stand offs The center of the framing hole is one 1 inch 25 4mm above the center of the horizontal...

Страница 10: ...2mm 11 3 4 298mm DV 48D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 8 5 8 220mm 8 1 2 216mm 6 7 16 164mm 11 1 16 281mm 6 1 2 165mm 8 1 2 216mm 5 1 16 129mm 8 5 8 220mm 35 3 4 908mm DV 12 17D 12 17 305 432mm...

Страница 11: ...nner pipe 6 5 8 inch outer pipe 120 3048mm 24 610mm 36 914mm 60 1524mm 9 1 4 6 5 8 6 1 2 6 3 8 6 1 2 9 5 8 9 5 8 6 5 8 6 3 8 8 3 4 SL 09D 12 17 SL 12 17D SL12 17D SL 24D SL 36D SL 48D 47 3 4 35 3 4 23...

Страница 12: ...D SL D SERIES COMPONENTS IN ANY VENT SYSTEM CONFIGURATION Identifying Vent Components Approved vent system components are labeled for identi fication NO OTHER VENTING SYSTEMS OR COMPO NENTS MAY BE USE...

Страница 13: ...tion in total H when using flex vent except when using the simple up and out installation see Figure 9 Figure 9 Flex Vent The flex vent must be supported with the spacing between support intervals not...

Страница 14: ...MAX 40 FT 12 2m MODEL QV36 2 5 FT 863mm 3 FT 914mm 4 FT 1 22m 6 FT 1 86m 8 FT 2 48m 16 FT 4 8m MODEL QV32 V MIN H MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 9...

Страница 15: ...2 48 m H H1 16 MAX 4 8m Figure 14 Venting with Two 90 Elbows V FT H H1 FT 1 MIN 305 mm 2 MAX 610 mm 2 MIN 610 mm 4 MAX 1 22 m 3 MIN 914 mm 6 MAX 1 86 m 4 MIN 1 22 m 8 MAX 2 48 m H H1 8 MAX 2 48 m V H...

Страница 16: ...T 914mm 4 FT 1 22m 6 FT 1 86m 8 FT 2 48m 16 FT 4 8m MODEL QV32 V MIN H H1 MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 914mm 6 FT 1 86m 4 FT 1 22m 8 FT 2 48m 5...

Страница 17: ...2m 6 FT 1 86m 8 FT 2 48m 16 FT 4 8m MODEL QV32 V MIN H MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 914mm 6 FT 1 86m 4 FT 1 22m 8 FT 2 48m 5 FT 1 52m 16 FT 4 8m...

Страница 18: ...H1 16 MAX 4 8m V H H H1 1 MIN 305 mm 2 MAX 610 mm 4 MAX 1 22m 2 MIN 610 mm 4 MAX 1 22 m 8 MAX 2 48m 3 MIN 914 mm 6 MAX 1 86 m 12 MAX 3 72m 4 MIN 1 22 m 8 MAX 2 48 m 16 MAX 4 8m V H H1 H2 40 MAX 12 4...

Страница 19: ...TING WITH THREE 3 90o ELBOWS NATURAL GAS V H V1 H1 MAX 40 FT 12 2m VENTING WITH THREE 3 90o ELBOWS PROPANE MODEL QV32 MODEL QV36 V MIN H MAX H H1 MAX H MAX H H1 MAX 90o Elbow on Top 2 5 FT 863mm 5 FT...

Страница 20: ...2 5 FT 863mm 3 FT 914mm 4 FT 1 22m 6 FT 1 86m 8 FT 2 48m 16 FT 4 8m MODEL QV32 V MIN H H1 MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 914mm 6 FT 1 86m 4 FT 1 2...

Страница 21: ...NATURAL AND PROPANE GAS V MIN H MAX 2 609mm 5 1 52m V1 MIN H1 MAX V2 MIN 5 1 52m 5 1 52m 4 5 1 37m V V1 V2 H H1 MAX 40 12 2m V H V2 V1 H1 NOTE There MUST be a 25 reduction in total H when using flex...

Страница 22: ...Out Top WARNING THE REAR VENT COLLAR SEAL CAP MUST REMAIN ATTACHED TO THE REAR VENTCOLLARSIFTHEVENTSYSTEMISATTACHED TO THE TOP STARTING COLLARS SEE FIGURE 21 WARNING FAILURE TO REMOVE INSULA TION IN T...

Страница 23: ...ther interior or exterior walls Cut a 12 x 12 305mm x 305mm hole through the wall for D series or a 10 x 10 254mm x 254mm hole for SL D series pipe The center of the framing hole is one 1 inch 25 4mm...

Страница 24: ...9 Attic Firestop JOIST CEILING FIRESTOP CEILING NAILS 4 REQUIRED CEILING CEILING FIRESTOP RAFTER NAILS 4 REQUIRED CEILING NEW FRAMING MEMBERS EXISTING CEILING JOISTS CHIMNEY HOLE 11 280 mm or 10 254 m...

Страница 25: ...RONGLY RECOMMENDED WHENEVER POSSIBLE TO USE THE VINYL PROTECTOR KIT 30 minimum for vinyl clad soffits a vent shall not terminate directly above a sidewalk or paved driveway which is located between tw...

Страница 26: ...MUM HEIGHTS PROVID ED THE TERMINATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICAL WALL AND 2 FEET BELOW A HORIZONTAL OVERHANG NOTE This also pertains to vertical vent systems in stalled on the outside...

Страница 27: ...oning Leveling and Securing of a Fireplace Figure 34 Gas Control System STANDING PILOT Step 5 The Gas Control Systems WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL The gas control system used with...

Страница 28: ...diameter and it does not penetrate the actual firebox Open the fireplace lower grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attaching the pipe...

Страница 29: ...installed Wall Switch Position the wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch p...

Страница 30: ...DE SEAL JOINT 0 1 4 FINISH MATERIAL MAY BE COMBUSTIBLE TOP AND SIDES OF UNIT Optional Accessories Optional fan and remote control kits require that 110 120 VAC be wired to the fireplace junction box W...

Страница 31: ...ANSI Z97 1 1984 and CPSC 16 CFR 1202 Safety Glazing Certification Council SGCC 1595 and 1597 Architec tural Testing Inc Reports 02 31919 01 and 02 31917 01 This statement is in compliance with CPSC 16...

Страница 32: ...r If it is necessary to access the pilot remove the trim door and glass door THERMOCOUPLE PILOT THERMOPILE 5 To put the control in the PILOT position turn the control knob counter clockwise to the PIL...

Страница 33: ...the gas supply lines When first lighting the fireplace it will take a few minutes for the lines to purge themselves of this air Once the purging is complete the fireplace will light and will operate...

Страница 34: ...urrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check of your fireplace s flame patterns Make sure the fla...

Страница 35: ...the pilot and hold the valve knob in If the millivolt reading is less than 15mV replace the thermocouple b Defective valve If the thermocouple is producing more than 15 millivolts replace faulty valve...

Страница 36: ...downwards lope is 1 4 inch d Glass too loose and air tight packet leaks in corners after usage Tighten the corner e Bad thermopile or thermocouple Replace if necessary f Improper vent cap installation...

Страница 37: ...ning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items and installation of upgraded component parts do not quality for a...