12

Installing the Fireplace

Step 1. Locating the Fireplace

Space and clearance requirements for locating a fireplace
within a room (see Figure 3).

Minimum Clearances

 from the Fireplace to Combustible Materials

Inches

mm

Glass Front ...................................... 36 ........ 914
Floor .................................................. 0 ........... 0
Rear ................................................ 1/2 ........ 13
Sides ............................................... 1/2 ........ 13
Top  (QV32) .................................. 1 1/2 ....... 38
        (QV36) .................................. 3 1/4 ....... 83
Ceiling* ............................................. 31 ........ 787

For minimum clearances, see the direct vent termination
clearance diagrams in Figures 30 and 31 in this manual.

Minimum Clearances

 from the Vent Pipe to Combustible Materials

Inches

mm

Vertical Sections

. ............. 1 ................ 25

Horizontal Sections

Top ..................................... 3 ................ 75

Bottom ................................ 1 ................ 25

Sides .................................. 1 ................ 25

At Wall Firestops

Top .................................. 2 1/2 ............ 63.7

Bottom .............................. 1/2 ............... 13

Sides .................................. 1 ................ 25

* The clearance to the ceiling is measured from the top

of the unit, excluding the standoffs (see Figure 38).

The distance from the unit to combustible construction is
to be measured from the unit outer wrap surface to the
combustible construction, 

NOT

 from the screw heads that

secure the unit together.

A

B

C

D

E

                  QV36

42”

16 1/4”

31 7/8”

45”

63 3/4”

                  QV32

37”

16 1/4”

29 3/8”

41 1/2”

58 3/4”

1/2 “ MIN. (13mm)

C

3” MIN. (76mm)

A

B

D

E

Clearance Requirements

The top and back of the fireplace are defined by stand-
offs. The minimum clearance to a perpendicular wall
extending past the face of the fireplace is 3 inches (76mm).
The back of the fireplace may be recessed 16 1/4 inches
(413mm) into combustible construction.

   Figure 3.    Fireplace Dimensions, Locations,
                     and Space Requirements

Constructing the Fireplace Chase

A chase is a vertical box-like structure built to enclose the
gas fireplace and/or its vent system. Vertical vents that run
on the outside of a building may be, but are not required to
be, installed inside a chase.

CAUTION: TREATMENT OF FIRESTOP SPACERS AND
CONSTRUCTION OF THE CHASE MAY VARY WITH THE
TYPE OF BUILDING. THESE INSTRUCTIONS ARE NOT
SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL
BUILDING CODES. THEREFORE, YOUR LOCAL BUILD-
ING CODES MUST BE CHECKED TO DETERMINE THE
REQUIREMENTS FOR THESE STEPS.

Factory-built fireplace chases should be constructed  in
the manner of all outside walls of the home to prevent cold
air drafting problems. The chase should not break the out-
side building envelope in any manner.

This means that the walls, ceiling, base plate and cantile-
ver floor of the chase should be insulated. Vapor and air
infiltration barriers should be installed in the chase as per
regional codes for the rest of the home. Additionally, Alad-
din Hearth Products recommends that the inside surfaces
be sheetrocked and taped for maximum air tightness.

To further prevent drafts, the firestops should be caulked
to seal gaps. Gas line holes and other openings should be
caulked or stuffed with insulation. If the unit is being in-
stalled on a cement slab, we recommend that a layer of
plywood be placed underneath to prevent conducting cold
up into the room. Be sure to include spark arrestors for
woodburning units if they are required.

THE CHASE SHOULD BE CONSTRUCTED SO THAT
ALL CLEARANCES TO THE FIREPLACE ARE MAIN-
TAINED AS SPECIFIED WITHIN THIS INSTALLERS
GUIDE.

Содержание QV32

Страница 1: ...LIANCE FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home where not prohibit ed by local codes 2 This appliance is only for use with...

Страница 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Страница 3: ...nstalling Vent Components 26 C Vent Termination 28 Step 4 Positioning Leveling and Securing the Fireplace 31 Step 5 The Gas Control Systems 31 Step 6 The Gas Supply Line 32 Step 7 Gas Pressure Require...

Страница 4: ...Installers Guide have been tested to certification standards and listed by the applicable laboratories Certification MODELS QV32 QV36 LABORATORY Underwriters Laboratories TYPE Direct Vent Gas Firepla...

Страница 5: ...re to follow these instructions will void the owner s warranty and may present a fire hazard The Quadra Fire Warranty will be voided by and Aladdin Hearth Products disclaims any responsibility for the...

Страница 6: ...61mm 30 3 4 780mm 15 3 8 390mm 15 3 4 402mm 36 917mm 41 1040mm 3 1 2 90mm 8 198mm ELECTRICAL ACCESS 26 7 8 682mm 8 5 8 219mm 6 5 8 168mm 16 1 4 415mm 8 3 4 223mm 1 2 14mm 24 610mm 34 1 2 879mm HEAT SH...

Страница 7: ...mm 16 1 4 415mm 1 2 14mm 32 1 2 827mm 2 1 4 55mm 5 1 16 129mm GAS LINE ACCESS 31 790mm 36 913mm 3 1 2 90mm 8 198mm ELECTRICAL ACCESS 23 3 8 593mm 8 5 8 219mm 6 5 8 168mm 20 1 2 521mm 31 789mm HEAT SHI...

Страница 8: ...structing the Fireplace Chase A chase is a vertical box like structure built to enclose the gas fireplace and or its vent system Vertical vents that run on the outside of a building may be but are not...

Страница 9: ...raming should be constructed of 2 X 4 lumber or heavier The framing headers may rest on the fireplace stand offs The center of the framing hole is one 1 inch 25 4mm above the center of the horizontal...

Страница 10: ...2mm 11 3 4 298mm DV 48D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 8 5 8 220mm 8 1 2 216mm 6 7 16 164mm 11 1 16 281mm 6 1 2 165mm 8 1 2 216mm 5 1 16 129mm 8 5 8 220mm 35 3 4 908mm DV 12 17D 12 17 305 432mm...

Страница 11: ...nner pipe 6 5 8 inch outer pipe 120 3048mm 24 610mm 36 914mm 60 1524mm 9 1 4 6 5 8 6 1 2 6 3 8 6 1 2 9 5 8 9 5 8 6 5 8 6 3 8 8 3 4 SL 09D 12 17 SL 12 17D SL12 17D SL 24D SL 36D SL 48D 47 3 4 35 3 4 23...

Страница 12: ...D SL D SERIES COMPONENTS IN ANY VENT SYSTEM CONFIGURATION Identifying Vent Components Approved vent system components are labeled for identi fication NO OTHER VENTING SYSTEMS OR COMPO NENTS MAY BE USE...

Страница 13: ...tion in total H when using flex vent except when using the simple up and out installation see Figure 9 Figure 9 Flex Vent The flex vent must be supported with the spacing between support intervals not...

Страница 14: ...MAX 40 FT 12 2m MODEL QV36 2 5 FT 863mm 3 FT 914mm 4 FT 1 22m 6 FT 1 86m 8 FT 2 48m 16 FT 4 8m MODEL QV32 V MIN H MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 9...

Страница 15: ...2 48 m H H1 16 MAX 4 8m Figure 14 Venting with Two 90 Elbows V FT H H1 FT 1 MIN 305 mm 2 MAX 610 mm 2 MIN 610 mm 4 MAX 1 22 m 3 MIN 914 mm 6 MAX 1 86 m 4 MIN 1 22 m 8 MAX 2 48 m H H1 8 MAX 2 48 m V H...

Страница 16: ...T 914mm 4 FT 1 22m 6 FT 1 86m 8 FT 2 48m 16 FT 4 8m MODEL QV32 V MIN H H1 MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 914mm 6 FT 1 86m 4 FT 1 22m 8 FT 2 48m 5...

Страница 17: ...2m 6 FT 1 86m 8 FT 2 48m 16 FT 4 8m MODEL QV32 V MIN H MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 914mm 6 FT 1 86m 4 FT 1 22m 8 FT 2 48m 5 FT 1 52m 16 FT 4 8m...

Страница 18: ...H1 16 MAX 4 8m V H H H1 1 MIN 305 mm 2 MAX 610 mm 4 MAX 1 22m 2 MIN 610 mm 4 MAX 1 22 m 8 MAX 2 48m 3 MIN 914 mm 6 MAX 1 86 m 12 MAX 3 72m 4 MIN 1 22 m 8 MAX 2 48 m 16 MAX 4 8m V H H1 H2 40 MAX 12 4...

Страница 19: ...TING WITH THREE 3 90o ELBOWS NATURAL GAS V H V1 H1 MAX 40 FT 12 2m VENTING WITH THREE 3 90o ELBOWS PROPANE MODEL QV32 MODEL QV36 V MIN H MAX H H1 MAX H MAX H H1 MAX 90o Elbow on Top 2 5 FT 863mm 5 FT...

Страница 20: ...2 5 FT 863mm 3 FT 914mm 4 FT 1 22m 6 FT 1 86m 8 FT 2 48m 16 FT 4 8m MODEL QV32 V MIN H H1 MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 914mm 6 FT 1 86m 4 FT 1 2...

Страница 21: ...NATURAL AND PROPANE GAS V MIN H MAX 2 609mm 5 1 52m V1 MIN H1 MAX V2 MIN 5 1 52m 5 1 52m 4 5 1 37m V V1 V2 H H1 MAX 40 12 2m V H V2 V1 H1 NOTE There MUST be a 25 reduction in total H when using flex...

Страница 22: ...Out Top WARNING THE REAR VENT COLLAR SEAL CAP MUST REMAIN ATTACHED TO THE REAR VENTCOLLARSIFTHEVENTSYSTEMISATTACHED TO THE TOP STARTING COLLARS SEE FIGURE 21 WARNING FAILURE TO REMOVE INSULA TION IN T...

Страница 23: ...ther interior or exterior walls Cut a 12 x 12 305mm x 305mm hole through the wall for D series or a 10 x 10 254mm x 254mm hole for SL D series pipe The center of the framing hole is one 1 inch 25 4mm...

Страница 24: ...9 Attic Firestop JOIST CEILING FIRESTOP CEILING NAILS 4 REQUIRED CEILING CEILING FIRESTOP RAFTER NAILS 4 REQUIRED CEILING NEW FRAMING MEMBERS EXISTING CEILING JOISTS CHIMNEY HOLE 11 280 mm or 10 254 m...

Страница 25: ...RONGLY RECOMMENDED WHENEVER POSSIBLE TO USE THE VINYL PROTECTOR KIT 30 minimum for vinyl clad soffits a vent shall not terminate directly above a sidewalk or paved driveway which is located between tw...

Страница 26: ...MUM HEIGHTS PROVID ED THE TERMINATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICAL WALL AND 2 FEET BELOW A HORIZONTAL OVERHANG NOTE This also pertains to vertical vent systems in stalled on the outside...

Страница 27: ...oning Leveling and Securing of a Fireplace Figure 34 Gas Control System STANDING PILOT Step 5 The Gas Control Systems WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL The gas control system used with...

Страница 28: ...diameter and it does not penetrate the actual firebox Open the fireplace lower grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attaching the pipe...

Страница 29: ...installed Wall Switch Position the wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch p...

Страница 30: ...DE SEAL JOINT 0 1 4 FINISH MATERIAL MAY BE COMBUSTIBLE TOP AND SIDES OF UNIT Optional Accessories Optional fan and remote control kits require that 110 120 VAC be wired to the fireplace junction box W...

Страница 31: ...ANSI Z97 1 1984 and CPSC 16 CFR 1202 Safety Glazing Certification Council SGCC 1595 and 1597 Architec tural Testing Inc Reports 02 31919 01 and 02 31917 01 This statement is in compliance with CPSC 16...

Страница 32: ...r If it is necessary to access the pilot remove the trim door and glass door THERMOCOUPLE PILOT THERMOPILE 5 To put the control in the PILOT position turn the control knob counter clockwise to the PIL...

Страница 33: ...the gas supply lines When first lighting the fireplace it will take a few minutes for the lines to purge themselves of this air Once the purging is complete the fireplace will light and will operate...

Страница 34: ...urrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check of your fireplace s flame patterns Make sure the fla...

Страница 35: ...the pilot and hold the valve knob in If the millivolt reading is less than 15mV replace the thermocouple b Defective valve If the thermocouple is producing more than 15 millivolts replace faulty valve...

Страница 36: ...downwards lope is 1 4 inch d Glass too loose and air tight packet leaks in corners after usage Tighten the corner e Bad thermopile or thermocouple Replace if necessary f Improper vent cap installation...

Страница 37: ...ning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items and installation of upgraded component parts do not quality for a...