Document: LT0439 Vigilant
MX1-Au
Operator Manual
Issue 1.73
23 October 2018
Page 6-9
Zone 001 Std Detection G1
Office
Press OK to confirm Disable
or CANCEL for no action
Fig 6-14 – Confirming Zone Disable
When a zone is disabled, the corresponding zone indicator will light
yellow.
If this zone is configured so that it cannot be disabled, a message,
“
This zone cannot be disabled
”, will be displayed briefly.
Do not press the f.b.p.
DISABLE
control when the Alarm List
is being shown unless the intent is to disable all alarms.
From the base display press
DISABLE
, then
ZONE
F1
. A single zone
or a range of zone numbers can be entered in this display:
Disable zone: | -to-
Enter nnn for single zone |
or nnn F1 nnn for a range |
F4 to backspace
| <-
Fig 6-15 – Entering Zones To Be Disabled or Enabled
Enter a single zone or the required range and press
OK
. For example:
If only zone 2 is to be disabled, this is entered as
2
OK
.
If the zone range 23 to 38 inclusive is to be enabled or disabled, this
would be entered as
2
3
F1
3
8
OK
.
F4
can be used as a backspace key to correct entry mistakes.
If a single zone has been entered, this display results;
Disabling or
Enabling a
Zone or a Zone
Range
Содержание MX1-Au
Страница 104: ...Vigilant MX1 Au Operator Manual Document LT0439 Page 23 October 2018 Issue 1 73 8 18 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 118: ...Vigilant MX1 Au Operator Manual Document LT0439 Page 23 October 2018 Issue 1 73 9 14 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 160: ...Vigilant MX1 Au Operator Manual Document LT0439 Page 23 October 2018 Issue 1 73 11 34 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 182: ...Vigilant MX1 Au Operator Manual Document LT0439 Page 23 October 2018 Issue 1 73 12 22 THIS PAGE INTENTIONALLY LEFT BLANK...