Document: LT0439 Vigilant
MX1-Au
Operator Manual
Issue 1.73
23 October 2018
Page 11-25
The I-HUB comes pre-configured for ring operation, with Port 5 (J4)
connected to the
MX1
serial port configured for networking.
Figure 11-21
– Network Ring Example
The I-HUB is powered by one of the
MX1
’s +VBF supplies. This supply
must not be used for any directly-connected field wiring, to ensure that
fuse failure caused by an external wiring fault does not disable the
network. Alternatively, the I-HUB (and fibre modems if included) could be
powered off the Loop Interface Supply terminals J33 using a fused power
lead (e.g., a spare LM0459 supplied with an
MX
Loop Card). The I
HUB’s
J4 TTL serial port is connected using loom LM0152 to whichever serial
port (0, 2, 3 or 4) is configured in the
MX1
for networking as shown in
Figure 11-22.
Figure 11-22
– I-HUB to MX1 Wiring
I-HUB Wiring
I-HUB
Port 1
I-HUB
Port 2
I-HUB
Port 1
I-HUB
Port 2
I-HUB
Port 1
I-HUB
Port 2
LM0152
MX1
Controller Board
I-HUB Board
J4 Port 5
2
3
4
0
Power
MX1
Serial
Ports
+24V
0V
+24V
0V
Содержание MX1-Au
Страница 104: ...Vigilant MX1 Au Operator Manual Document LT0439 Page 23 October 2018 Issue 1 73 8 18 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 118: ...Vigilant MX1 Au Operator Manual Document LT0439 Page 23 October 2018 Issue 1 73 9 14 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 160: ...Vigilant MX1 Au Operator Manual Document LT0439 Page 23 October 2018 Issue 1 73 11 34 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 182: ...Vigilant MX1 Au Operator Manual Document LT0439 Page 23 October 2018 Issue 1 73 12 22 THIS PAGE INTENTIONALLY LEFT BLANK...