Troubleshooting
84
Diagnosis
(continued)
Faults with fault display on the programming unit
(continued)
Fault code
in display
Behaviour of system
Cause of fault
Action
c1
Boiler cools down
External safety equipment
Check connection of plug
aBÖ
Check external safety
equipment (see page 40)
c2
Controlled operation
Open circuit
KM-BUS to solar control
Check KM-BUS connection and
solar control. Without solar
control, set coding address
“54: 0”
c4
Controlled operation
Fault
Input module 0-10V
Check all connections, cables etc.
Replace function expansion
module; without expansion
module set coding address
“9d: 0”
c8
Boiler cools down
Fault
Low water indicator
Check water level of system,
reset low water indicator
c9
Boiler cools down
Fault
Maximum pressure limiter
Check system pressure, reset
maximum pressure limiter
ca
Boiler cools down
Fault
Minimum pressure limiter or
maximum pressure limiter 2
Check system pressure, reset
minimum or maximum pressure
limiter
cb
Boiler cools down
Fault
Additional fixed high limit
Check system pressure, reset
fixed high limit, reset flue gas
damper
cd
Controlled operation
Communication fault
Vitocom 300
Check connections and
Vitocom 300
cEe
Controlled operation
Communication fault
Plug-in adaptor for external safety
equipment
Check plug-in adaptor for
external safety equipment
cf
Controlled operation
Fault
LON communication module
Replace communication module
d1
Boiler cools down
Burner fault
Check burner
d4
Boiler cools down
Fixed high limit has operated
Check fixed high limit
d6
Controlled operation
Fault at DE1 in the plug-in
adaptor for external safety equipment
Check connection at inputs DE1
to DE3
d7
Controlled operation
Fault at DE2 in the plug-in
adaptor for external safety equipment
d8
Controlled operation
Fault at DE3 in the plug-in
adaptor for external safety equipment
da
Controlled operation without
influence of room
temperature
Short circuit
Room temperature sensor, system
circuit A1
Check room temperature sensor
(see page 112)
db
Controlled operation without
influence of room
temperature
Short circuit
Room temperature sensor,
mixing valve circuit M2
Check room temperature sensor
(see page 112)
5285
941
-
0
1
Содержание VITOTRONIC 300 GW2
Страница 19: ...Installation 19 Overview of electrical connections for VD2 VD2A CT3 only 5285 941 01...
Страница 20: ...Installation 20 Overview of electrical connections for CM2 only 5285 941 01...
Страница 138: ...Additional information 138 Wiring diagram continued 120 V motherboard 5285 941 01 A11 A3 float ing ON ON...
Страница 143: ...143 5285 941 01...
Страница 144: ...144 5285 941 01...
Страница 145: ...145 5285 941 01...