Additional information
121
Coding 2
(continued)
Overview of all codings
(continued)
Coding as per
factory setting
Address: Value
Function
New coding
Address:
Value
Possible change
4A: 0
General
Plug
aJ
A
not installed
4A: 1
Plug
aJ
A
installed (e.g. temperature sensor of
Therm-Control);
automatically recognized
4b: 0
General
Plug
aJ
B
not installed
4b: 1
Plug
aJ
B
installed (e.g. temperature sensor
T2); automatically recognized
4C: 0
General
Connection at plug
sÖ
A1:
4C: 1
Primary pump of DHW tank loading system
p g
sÖ
Heating circuit pump
4C: 2
Switch contact of Therm-Control
4C: 3
Circulation pump of flue gas/water heat
exchanger
4d: 1
General
Connection at plug
sL
:
Shunt pump
4d: 2
Boiler circuit pump
4E: 0
General
Connection at plug
gS
:
3-way mixing valve for return
temperature control
4E: 1
3-way valve of DHW tank loading system
4F: 5
General
Shunt pump with 5 minutes
4F: 0
Shunt pump without run-on time
p
p
run-on time
4F: 1
to
4F: 60
Run-on time adjustable from 1 to 60 minutes
54: 0
General
Without solar control
54: 1
With Vitosolic 100; automatically recognized
54: 2
With Vitosolic 200; automatically recognized
55: 0
DHW
DHW tank heating,
differ/- 2.5 K
55: 1
Optimized DHW tank heating active
(takes into account the rate at which the DHW
tank temperature increases during domestic hot
water heating)
55: 2
DHW tank temperature control with 2 DHW
tank temperature sensors
55: 3
DHW tank temperature control of DHW tank
loading system
56: 0
DHW
Setting range of domestic
hot water temperature 10 to
60°C / 50 to 140°F
56: 1
Setting range of domestic hot water
temperature 10 to 95°C / 50 to 203°F
¨
Safety instruction!
Observe max. DHW temperature
Adjust adjustable high limit ”
R
”
58: 0
DHW
Without additional function
for domestic hot water
heating
58: 1
to
58: 95
Input of a 2nd desired DHW temperature value;
variable between 1 and 95°C / 34 and 203°F
(note coding address ”56”)
Please note:
The DHW tank is heated to the 2nd set-point
value during the 4th activation period for
domestic hot water heating (see operating
instructions regarding settings).
5285
941
-
0
1
Содержание VITOTRONIC 300 GW2
Страница 19: ...Installation 19 Overview of electrical connections for VD2 VD2A CT3 only 5285 941 01...
Страница 20: ...Installation 20 Overview of electrical connections for CM2 only 5285 941 01...
Страница 138: ...Additional information 138 Wiring diagram continued 120 V motherboard 5285 941 01 A11 A3 float ing ON ON...
Страница 143: ...143 5285 941 01...
Страница 144: ...144 5285 941 01...
Страница 145: ...145 5285 941 01...