Additional information
126
Coding 2
(continued)
Overview of all codings
(continued)
Coding as per
factory setting
Address: Value
Function
New coding
Address:
Value
Possible change
97: 2
General
The outdoor temperature of
the sensor connected to the
97: 0
Not transmitted to heating circuit controls
the sensor connected to the
control unit is transmitted
via the LON BUS to any
Vitotronic 200-H units
which may be connected
97: 1
The outdoor temperature is acepted by any
heating circuit controls which may be
connected
98: 1
General
Viessmann system number
(in conjunction with
monitoring of several
systems within one LON
BUS system)
98: 1
to
98: 5
System number selectable from 1 to 5
99: 0
General
Connection at terminals ”2”
and ”3” in plug
aVD
(E t
l di bl /”Cl
99: 1
Contact effective for:
Without function
(External disable/”Close
mixing valve” externally not
99: 2
”Close mixing valve”, mixing valve circuit M2
mixing valve externally not
active)
99: 3
Without function
99: 4
”Close mixing valve”, mixing valve circuit M3
99: 5
Without function
99: 6
”Close mixing valve”, mixing valve circuits M2
and M3
99: 7
Without function
99: 8
External disable
99: 9
Without function
99: 10
External disable and ”Close
mixing valve”, mixing valve circuit M2
99: 11
Without function
99: 12
External disable and ”Close
mixing valve”, mixing valve circuit M3
99: 13
Without function
99: 14
External disable and ”Close mixing valve”,
mixing valve circuits M2 and M3
99: 15
Without function
9A: 0
General
Connection at terminals ”1”
and ”2” in plug
aVD
(”O
i i
l ”
9A: 1
Contact effective for:
Without function
(”Open mixing valve”
externally not active)
9A: 2
”Open mixing valve”, mixing valve circuit M2
externally not active)
9A: 3
Without function
9A: 4
”Open mixing valve”, mixing valve circuit M3
9A: 5
Without function
9A: 6
”Open mixing valve”, mixing valve circuits M2
and M3
9A: 7
Without function
9b: 70
General
Desired supply temperature
70 °C / 158 °F i h
9b: 0
Input
aVH
blocked
pp y
p
70 °C / 158 °F with
external request (input
aVH
)
9b: 1
to
9b: 127
Desired supply temperature selectable from
1 to 127°C / 34 to 261°F
5285
941
-
0
1
Содержание VITOTRONIC 300 GW2
Страница 19: ...Installation 19 Overview of electrical connections for VD2 VD2A CT3 only 5285 941 01...
Страница 20: ...Installation 20 Overview of electrical connections for CM2 only 5285 941 01...
Страница 138: ...Additional information 138 Wiring diagram continued 120 V motherboard 5285 941 01 A11 A3 float ing ON ON...
Страница 143: ...143 5285 941 01...
Страница 144: ...144 5285 941 01...
Страница 145: ...145 5285 941 01...