Service Equipment
Service
Tools
Assortment of flathead and Phillips screwdrivers
Pipe wrenches
Open-ended wrenches
Pipe sealant
Assortment of Hex keys
Flashlight
Cleaning supplies
Plastic hand brush
Cleaning/service brush
Vacuum cleaner
Clean rags
Testing/analysis equipment
(use only calibrated equipment)
Multimeter to measure 0-120VAC, 0-25 amps AC
and 0-100 microamps DC.
Technical information
The following is a list of literature applicable to the
Vitotrans 300:
Installation, Operating and Service Instructions
Technical Data Manual
Wiring diagrams
For installation of the heating system, please refer also
to the technical literature of other Viessmann System
Technology devices:
Installation Instructions for accessories
Installation Instructions for Viessmann hot water
heating boilers
Replacement parts
For a complete listing of replacement components, please
see Parts List starting on page 75 of these instructions.
Order replacement components from your Viessmann
distributor.
CAUTION
Use only original Viessmann recommended components
when replacing defective parts. Installation of incorrect
replacement parts can cause hazardous operation and
will void warranty.
Service and Cleaning
IMPORTANT
Inspection and (if necessary) cleaning of unit must take
place within 2 years of initial start-up and as required
thereafter. Reinspection time must not exceed 2 years.
The internal cleaning of the Vitotrans including its potable
water connections may only be performed by a licensed
professional heating contractor. There are no user
serviceable parts on this equipment.
Clean the Vitotrans enclosure with a commercially
available alcohol-based glass cleaning agent and a soft
clean cloth.
If a water softener system is used in the domestic cold
water inlet piping into the Vitotrans, the water treatment
system should be inspected (serviced) at the same time.
If a drinking water filter is used in the main line, the
filter cartridge should also be investigated. All external
equipment must be serviced regularly and function
properly.
For water quality requirements refer to page 29.
For maintenance schedule refer to page 87.