58
5833 275 - 04
Vitotrans 300 Installation, Operating and Service
System Pump
Service
1. On a dual pump system, locate the faulty pump.
and remove pump head cover.
IMPORTANT
Refer to completion of service starting on page 65.
Note:
To determine the pump service procedure required,
see ‘System pump fault codes’ on page 61.
1. With the pump head cover off, disconnect cables from
the communication card.
2. Remove mounting screw.
3. Remove card by pulling straight out from the pump head.
4. Replace card, reconnect wires and pump head cover.
Replacing pump communication card
WARNING
DISCONNECT POWER BEFORE SERVICING THE VITOTRANS.
Note:
The Vitotrans 300 is equipped with a variable speed
internal heating system pump, that has been
configured specifically for that Vitotrans 300 model.
WARNING
Do not attempt to alter the configuration of the internal
pump. In case of replacement, only use genuine
Viessmann replacemenrt parts. Failure to do so will
compromise the functionality of the Vitotrans 300.
IMPORTANT
Allow to cool before servicing. See preparing for service
starting on page 53.