Vitotrans 300 Installation, Operating and Service
Installation
Connecting to the Heating System - Closely Spaced Tees
Connecting to the Heating System - Low Loss Header
Legend
A
Vitotrans 300
B
Vitotrans supply
C
Vitotrans return
D
Heating system supply
Legend
A
Vitotrans 300
B
Vitotrans supply
C
Vitotrans return
D
Connection to heating equipment
*
Maximum spacing between tees is 4X the pipe diameter.
Branch off from main heating system supply and
return from the system side of the low loss header.
Branch off from main heating
system supply.
The system heat source (boiler) should be set to supply
water to the Vitotrans 300 at least 20ºF (11ºC) higher
than the desired DHW setpoint. It is recommended that
the Vitotrans 300 is connected close to the heat source.
The system heat source (boiler) should be set to supply
water to the Vitotrans 300 at least 20ºF (11ºC) higher
than the desired DHW setpoint. It is recommended that
the Vitotrans 300 is connected close to the heat source.
*
*