Vitotrans 300 Installation, Operating and Service
Installation
Vitotrans 300 BACnet (IP) Points
(continued)
Name
Object ID
Read / Write Note / Description
Boiler Dmd
binaryOutput:103 Writable
Do Not Change
DHW Recirc Pump Cmd
binaryOutput:104 Writable
Do Not Change
External Tank Loading Pump Cmd
binaryOutput:105 Writable
Do Not Change
Boiler Pump Cmd P1B
binaryOutput:106
Writable
Do Not Change
Language
binaryValue:1
Read / Write Language (English / French) - DISABLED
Units
binaryValue:2
Read / Write Units (Imperial / Metric)
External Tank
binaryValue:3
Read / Write External DHW Storage Tank (No / Yes)
DHW Recirculation
binaryValue:4
Read / Write DHW Recirculation Pump (No / Yes)
Reset Dead Lock
binaryValue:6
Read / Write Do Not Change
Service 1 HX
binaryValue:7
Read / Write Service Mode (No / Yes)
Comfort mode
binaryValue:9
Read / Write Comfort Mode (No / Yes)
DHW Flow Presence
binaryValue:11
Read / Write Do Not Change
Boiler Flow Presence
binaryValue:12
Read / Write Do Not Change
Reset System Runtime
binaryValue:13
Read / Write Do Not Change
Tank Sanitation Mode
binaryValue:14
Read / Write Tank Sanitation Function (No / Yes)
Fault - System Pump Comms
binaryValue:20
Read / Write System Pump Communication
(Normal / Fault)
Fault - DHW Flow Sensor
binaryValue:21
Read / Write Flow Sensor (Normal / Fault)
Fault - System Pump Deadhead
binaryValue:22
Read / Write System Pump Deadhead (Normal/Fault)
Fault - DHW Temp Sensor
binaryValue:23
Read / Write DHW Temp Sensor (Normal / Fault)
Fault - Fixed High Limit
binaryValue:24
Read / Write Fixed High Limit (Normal / Fault)
Fault - Fixed High Limit
binaryValue:25
Read / Write DCW Temp Sensor (Normal / Fault)
Fault - System Return Temp Sensor
binaryValue:26
Read / Write Return Temp Sensor (Normal / Fault)
Fault - DHW Tank Temp Sensor
binaryValue:27
Read / Write Tank Temp Sensor (Normal / Fault)
Fault - General Fault
binaryValue:30
Read / Write General Fault (Normal / Fault) -
generated by any fault
PID DHW Stpt
loop:1
Read only
Do Not Change
PID P1 Limit
loop:2
Read only
Do Not Change
Alarm_Class-notificationClass
notificationClass:1 Read only
Do Not Change
DHW Recirc Pump Schedule
schedule:1
Read only
Do Not Change
DHW Recirc Pump Schedule 1
schedule:2
Read only
Do Not Change
Fault - System Pump
multiStateValue:1 Read / Write System Pump Fault (Normal / Fault)
Warning - System Pump
multiStateValue:2 Read / Write System Pump Warning (Normal / Fault)
DHW Temp T1A Trend Log-recordCount
trendLog:100101
Read only
Do Not Change
DCW Temp T2 Trend Log-recordCount
trendLog:100103 Read only
Do Not Change
Flow Rate DHW Trend Log-recordCount
trendLog:100104 Read only
Do Not Change
Boiler Return Temp T4 Trend Log-recordCount
trendLog:100105 Read only
Do Not Change
External Tank Temp T5 Trend Log-recordCount
trendLog:100107 Read only
Do Not Change
Boiler Supply Temp T3 Trend Log-recordCount
trendLog:300010 Read only
Do Not Change
Boiler Flow Rate Trend Log-recordCount
trendLog:300011 Read only
Do Not Change
DHW Temp T1A_C Trend Log-recordCount
trendLog:300020 Read only
Do Not Change
DCW Temp T2_C Trend Log-recordCount
trendLog:300021 Read only
Do Not Change
Boiler Return Temp T4_C Trend Log-recordCount
trendLog:300022 Read only
Do Not Change
External Tank Temp T5_C Trend Log-recordCount trendLog:300023 Read only
Do Not Change
Boiler Supply Temp T3_C Trend Log-recordCount trendLog:300025 Read only
Do Not Change
Flow Rate Boiler_LPM Trend Log-recordCount trendLog:300027 Read only
Do Not Change