10.2 Vitosolic 100, type SD1, part no. Z007 387
Specification
Construction
The control unit comprises:
■ PCB
■ LCD
■ Selector keys
■ Connection terminals
– Sensors
– Solar circuit pump
– KM BUS
– Power supply (on-site ON/OFF switch)
■ PWM output for controlling the solar circuit pump
■ Relay for actuating pumps and valves
The standard delivery includes collector temperature sensor and cyl-
inder temperature sensor.
Collector temperature sensor
For connection inside the appliance.
On-site extension of the connecting lead:
■ 2-core lead, length up to 60 m with a cross-section of 1.5 mm
2
(cop-
per)
■ Never route this lead immediately next to 230/400 V cables
Lead length
2.5 m
IP rating
IP 32 to EN 60529; ensure
through design/installation
Sensor type
Viessmann NTC 20 kΩ at
25 °C
Permissible ambient temperature
– during operation
−20 to +200 °C
– during storage and transport
−20 to +70 °C
Cylinder temperature sensor
For connection inside the appliance.
On-site extension of the connecting lead:
■ 2-core lead, length up to 60 m with a cross-section of 1.5 mm
2
(cop-
per)
■ Never route this lead immediately next to 230/400 V cables
Lead length
3.75 m
IP rating
IP 32 to EN 60529; ensure
through design/installation
Sensor type
Viessmann NTC 10 kΩ at
25 °C
Permissible ambient temperature
– during operation
0 to +90 °C
– during storage and transport
−20 to +70 °C
For systems with Viessmann DHW cylinders, the cylinder temperature
sensor is installed in the threaded elbow (see chapter "Specification"
of the relevant DHW cylinder and chapter "Installation accessories")
in the heating water return.
Functions
■ Switching the solar circuit pump for DHW and/or swimming pool
heating
■ Electronic limiter for the temperature in the DHW cylinder (safety
shutdown at 90 °C)
■ Collector safety shutdown
Information regarding auxiliary function for DHW heating and
suppression of reheating by the boiler
Systems with Vitotronic control units with KM BUS offer optional sup-
pression of reheating by the boiler and auxiliary function for DHW
heating.
Systems with other Viessmann control units only offer optional sup-
pression of reheating by the boiler.
For further functions, see chapter "Functions".
Specification
170
47
204
Rated voltage
230 V ~
Rated frequency
50 Hz
Rated current
4 A
Power consumption
2 W
(in standby mode 0.7 W)
Safety category
II
IP rating
IP 20 to EN 60529; ensure
through design/installation
Function
Type 1B to EN 60730-1
Permiss. ambient temperature
– during operation
0 to +40 °C for use in the living
space or boiler room (standard
ambient conditions)
– during storage and transport
−20 to +65 °C
Rated relay output breaking capaci-
ty
– Semi-conductor relay 1
0.8 A
– Relay 2
4(2) A, 230 V~
– Total
max. 4 A
Delivered condition
■ Vitosolic 100, type SD1
■ Cylinder temperature sensor
■ Collector temperature sensor
Tested quality
CE designation according to current EC Directives
Solar control units