11.5 Vitocell 300-B, type EVB
For DHW heating
in conjunction with boilers and solar collectors for dual mode operation.
Suitable for the following systems:
■ DHW temperature up to
95 °C
■ Heating water flow temperature up to
200 °C
■ Solar flow temperature up to
200 °C
■ Operating pressure
on the heating water side
up to
25 bar (2.5 MPa)
■ Operating pressure
on the solar side
up to
25 bar (2.5 MPa)
■ Operating pressure
on the DHW side
up to
10 bar (1.0 MPa)
Cylinder capacity
l
300
500
Indirect coil
upper
lower
upper
lower
DIN registration number
0100/08-10MC
Continuous output
For DHW heating from
10 to 45 °C
and a
heating water
flow temperature of … at the heating water flow rate stated
below
90 °C
kW
80
93
80
96
l/h
1965
2285
1965
2358
80 °C
kW
64
72
64
73
l/h
1572
1769
1572
1793
70 °C
kW
45
52
45
56
l/h
1106
1277
1106
1376
60 °C
kW
28
30
28
37
l/h
688
737
688
909
50 °C
kW
15
15
15
18
l/h
368
368
368
442
Continuous output
For DHW heating from
10 to 60 °C
and a
heating water
flow temperature of … at the heating water flow rate stated
below
90 °C
kW
74
82
74
81
l/h
1273
1410
1273
1393
80 °C
kW
54
59
54
62
l/h
929
1014
929
1066
70 °C
kW
35
41
35
43
l/h
602
705
602
739
Heating water flow rate
for the stated continuous flow rates
m
3
/h
5.0
5.0
5.0
5.0
Max. connectable heat pump output
At a heating water flow temperature of 55 °C and a DHW temperature
of 45 °C
For the specified heating water flow rate (both indirect coils connec-
ted in series)
kW
12
15
Standby heat loss q
BS
(standard parameter)
kWh/24 h
1.17
1.37
Standby capacity V
aux
l
149
245
Solar capacity V
sol
l
151
255
Dimensions
Length a (Ø)
– Incl. thermal insulation
mm
633
925
– Excl. thermal insulation
mm
–
715
Width b
– Incl. thermal insulation
mm
704
975
– Excl. thermal insulation
mm
–
914
Height c
– Incl. thermal insulation
mm
1779
1738
– Excl. thermal insulation
mm
–
1667
Height when
tilted
– Incl. thermal insulation
mm
1821
–
– Excl. thermal insulation
mm
–
1690
Weight
incl. thermal insulation
kg
114
125
Heating water content
l
11
11
11
15
Heating surface
m
2
1.50
1.50
1.45
1.90
Connections
(male thread)
Indirect coils
R
1
1¼
Cold water, DHW
R
1
1¼
DHW circulation
R
1
1¼
Information regarding the upper indirect coil
The upper indirect coil is intended to be connected to a heat genera-
tor.
Information regarding the lower indirect coil
The lower indirect coil is designed for connection to solar collectors.
To install the cylinder temperature sensor, use the threaded elbow with
sensor well provided in the standard delivery.
Information regarding continuous output
When engineering systems with the specified or calculated continuous
output, select a matching circulation pump. The stated continuous out-
put is only achieved when the rated boiler heating output ≥ continuous
output.
DHW cylinders
(cont.)