Installation in several rows, connection from the left or right
A
A
Collector temperature sensor
Horizontal installation on a pitched roof
1 collector array
A
With this type of connection, the "Relay kick" function on the
Vitosolic 200 must be enabled.
A
Collector temperature sensor
For this type of installation, ensure the following minimum flow rates
in the collector array (section):
4 m
2
35 l/(hm
2
)
5 m
2
30 l/(hm
2
)
≥6 m
2
25 l/(hm
2
)
3 m
2
45 l/(hm
2
)
< 2 m
2
65 l/(hm
2
)
2 or more collector arrays (≥ 4 m
2
)
A
With this type of connection, the
"Relay kick"
function on the
Vitosolic 200 must be enabled.
A
Collector temperature sensor
18.5 Installation examples Vitosol 200-T, type SP2A
Take ventilation into consideration when designing the collector arrays
(see chapter "Ventilation" on page 151).
Information regarding design and operation