IM 05F01D02-01E (1)

This manual describes installation, wiring, and other tasks required to make the indicator ready for operation.

Contents

1. Safety Precautions
2. Model and Suffix Codes
3. How to Install
4. How to Connect Wires
5. Hardware Specifications
6. Terminal Wiring Diagrams

Introduction

Thank you for purchasing the UM350/UM330 digital indicator with alarms.
The indicator is shipped from the factory with 3 hardcopy user’s manuals (A2 size). The 3 user’s manuals in hardcopy format
describe the operating procedures required for basic use.
It is recommended that you refer to these user’s manuals to understand [1] installation, [2] initial settings, and [3] operating
procedures of the indicator.

How to Use the Manuals

Purpose

Manual Title

Description

Media

Setup

Installation

 

Describes the tasks (installation, wiring, and others) required
to make the indicator ready for operations.

A2-size paper
(Front and back)

Basic operation 

Initial Settings 

Describes examples of setting PV input types, and alarm 
types. Making settings described herein allows you to carry
out basic monitoring.

A2-size paper
(Front)

(Back)

Operating 
procedures 
and troubleshooting 

Operations

 

Describes examples of setting alarm setpoints, as well as 
key operation necessary to run the indicator

Brief operation
and setpoint recording

Parameters

Contains the parameter map used as a guideline for setting
parameters and lists of parameters for recording user settings. 

A2-size paper
(Front and back)

1. Safety Precautions

The following symbol is indicated on the indicator to ensure safe use.

CAUTION

This symbol on the indicator indicates that the operator must refer to an explanation in the user’s manual in order to
avoid the risk of injury or death of personnel or damage to the instrument. The manual describes how the operator
should exercise special care to avoid electric shock or other dangers that may result in injury or loss of life.

The following symbols are used in the hardcopy user’s manuals.

NOTE

Indicates that operating the hardware or software in a particular manner may damage it or result in a system failure.

IMPORTANT

Draws attention to information that is essential for understanding the operation and/or features of the indicator.

 Exemption from Responsibility

Make sure that all of the precautions are strictly adhered to. Yokogawa Electric Corporation assumes no liability for any
damage resulting from use of the instrument in contradiction to the precautions.
Also, Yokogawa Electric Corporation assumes no liability to any party for any loss or damage, direct or indirect, caused
by the use or any unpredictable defect of the instrument.

 Regarding Protection, Safety, and Prohibition Against Unauthorized Modification

(1) In order to protect the product and the system controlled by it against damage and ensure its safe use, make certain that

all of the instructions and precautions relating to safety contained in this document are strictly adhered to. Yokogawa
does not guarantee safety if products are not handled according to these instructions.

(2) Modification of the product is strictly prohibited.

2. Model and Suffix Codes

Before using the indicator, check that the model and suffix codes match your order.

Model

Suffix Code

Description

UM350

UM330

Type

Digital indicator with Alarms (provided with retransmission output and 15 
V DC loop power supply as standard) 

-0

Standard type with three alarms

-3

Standard type with three alarms (with 24V DC loop power supply)

0

None

1

With communication and additional alarm-4 

2

With additional alarm-4

Optional functions

Check that the following items are provided:

• Digital indicator with alarms (of ordered model): ......................................... 1
• Brackets (mounting hardware): ...................................................................... 1 pair
• Unit label: ....................................................................................................... 1
• User’s Manuals: .............................................................................................. 3 (A2 size)
• User’s Manual (Reference) (CD-ROM Version)

(only for indicators with optional communication functions): ....................... 1

3. How to Install

NOTE

To install the indicator, select a location where:
(1) no one may accidentally touch the terminals,
(2) mechanical vibrations are minimal,
(3) corrosive gas is minimal,
(4) temperature can be maintained at about 23

°

C and the fluctuation is minimal,

(5) no direct radiant heat is present,
(6) no magnetic disturbances are caused,
(7) no wind blows against the terminal board (reference junction compensation

element),

(8) no water is splashed,
(9) no flammable materials are around,

Never place the indicator directly on flammable items or equipment.
If the indicator has to be installed close to flammable items or equipment, be sure to provide shielding panels all
around the indicator, at least 150mm away from every side; the panels should be made of either 1.43mm-thick
metal-plated steel plates or 1.6mm-thick uncoated steel plates.

NOTE

Never touch the opening at the bottom of the case. It is to be used in the factory at shipping.

Installation Position

Install the indicator at an angle within 30

°

 from horizontal with

the front panel facing upward. Do not install it facing down-
ward. The position of right and left sides should be horizontal.

External Dimensions and Panel Cutout Dimensions

(25)

(53)

[(N-1)

96+92]

117 min. 

145 min.

+0.8

0

+0.8

0

92

+0.8

0

92

+0.8

0

92

"N" stands for the number of indicators to be 
installed. 
However, the measured value applies if N 

 

5. 

100

11

UM350

General installation

Side-by-side close installation

1 to 10 mm (Panel thickness)

Small bracket 

Large bracket

91.8

112

Unit: mm 

96

96

48

UM330

96

100

11

1 to 10 mm (Panel thickness) 

Small bracket

Small bracket 

91.8

112

Unit: mm

145 min. 

General installation

Front of indicator

(53)

(25)

70 min. 

+0.8

0

92

+0.6

0

45

After opening the mounting hole on the
panel, follow the procedures below to in-
stall the indicator:
1.

Insert the indicator into the opening
from the front of the panel so that the
terminal board on the rear is at the far
side.

2.

Set the brackets in place on the top and
bottom of the indicator as shown in the
figure on the left, then tighten the screws
of the brackets. Take care not to over-
tighten them.

Note: Right and left mounting for UM330.

4. How to Connect Wires

CAUTION

1)

Before carrying out wiring, turn off the power to the indicator and check that the cables to be connected are not
alive with a tester or the like because there is a possibility of electric shock.

2)

For the protection and safe use of the indicator, be sure to place a circuit breaker (conforms with IEC60947,
5A, 100V or 220V AC) near the indicator where the breaker can easily be operated. In addition, be sure to
indicate that it is the instrument to cut the power supply of the indicator.

3)

Wiring must be carried out by personnel who have basic electrical knowledge and practical experience.

NOTE

1)

Provide power from a single-phase instrument power supply. If there is a lot of noise in the power line, insert an
insulating transformer into the primary side of the line and use a line filter (recommended part: ZAC2205-00U
from TDK) on the secondary side.
As a countermeasures against noise, do not place the primary and secondary power cables close to each other.

2)

For thermocouple input, use shielded compensating lead wires for wiring. For RTD input, use shielded wires
that have low conductor resistance and cause no significant differences in resistance between the three wires.
The cables to be used for wiring, terminal specifications, and recommended parts are as shown below.

3)

Alarm output relays have a life of 100,000 times that of the resistance load, use auxiliary relays to turn on/off
a load.

4)

The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves causes malfunction or
relay failure; always insert a CR filter for use with alternating current or a diode for use with direct current, as
a spark-removal surge suppression circuit, into the line in parallel with the load.

5)

When there is possibility of being struck by external lightening surge, use the arrester to protect the instrument.

For DC Relay Wiring

For AC Relay Wiring

R

UM350/UM330

UM’s contact 

Diode
(Mount it directly
 to the relay coil
 terminal (socket).) 

External DC power supply 

Relay

(Use one with a relay coil rating

 less than the UM’s contact rating.) 

Relay

    

R

UM350/UM330

UM’s contact 

CR filter 
(Mount it directly 
to the relay coil 
terminal (socket).)

External AC power supply 

Relay

(Use one with a relay coil

 rating less than the UM’s 

contact rating.) 

Cable Specifications and Recommended Cables

Purpose

Name and Manufacturer

Power supply, grounding, relay contact outputs

600 V PVC insulated wires, JIS C 3307, 0.9 to 2.0 mm

2

 

Thermocouple 

Shielded compensating lead wires, JIS C 1610,     X-    -        -  
(See Yokogawa Electric's GS 6B1U1-E.)

RTD

Shielded wires (three conductors), UL2482 (Hitachi Cable) 

Other signals

Shielded wires

Recommended Terminal Lugs

3 . 7 m m

7 mm or less

3 . 7 m m

7 mm or less

or

0.3 to 1.65 mm

2

0.8 N·m or less 

Applicable wire size

Tightening torque

Terminal Covers(Optional parts)

Target Model

Part Number

Sales Unit

UM350

T9115YD

1

UM330

T9115YE

1

Construction, Installation, and Wiring

• Construction: Only the front panel is dust-proof and drip-proof

(protection class IP55)
For side-by-side close installation the indicator loses its
dust-proof and drip-proof protection.

• Material: ABS resin and polycarbonate
• Case color: Black
• Weight: About 1 kg or less
• Dimensions:

UM350 

96 (W) 

 96 (H) 

 100 (depth from panel face)

mm

UM330 

96(W) 

 48 (H) 

 100 (depth from panel face)

mm

• Installation: Panel-mounting type. With top and bottom (or right

and left) mounting hardware (1 each)

• Panel cutout dimensions:

UM350 

92

+0.8

0

  (W) 

 92

+0.8

0

  (H) mm

UM330 

92

+0.6

0

  (W) 

 45

+0.8

0

  (H) mm

• Installation position: Up to 30

°

 upward facing

(not designed for facing downward)

• Wiring: M3.5 screw terminals (for signal wiring and power/

ground wiring as well)

Power Supply Specifications

• Power supply: Rated voltage of 100 to 240 V AC (

10%), 50/60 Hz

• Power consumption: Max. 20 VA (8.0 W max.)
• Internal fuse rating: 250 V AC, 1.6A  time-lug fuse
• Data backup: Non-volatile memory (can be written to up to

100,000 times)

• Withstanding voltage

- Between primary terminals* and secondary terminals**:

At least 1500 V AC for 1 minute

- Between primary terminals* and grounding terminal:

At least 1500 V AC for 1 minute

- Between grounding terminal and secondary terminals**:

At least 1500 V AC for 1 minute

- Between secondary terminals**:

At least 500 V AC for 1 minute

* Primary terminals indicate power terminals and relay

output terminals

** Secondary terminals indicate analog I/O signal, and

contact input terminals

• Insulation resistance: 20 M

 or more at 500 V DC between

power terminals and grounding terminal

• Grounding: Class D grounding (grounding resistance of 100 

or less)

Signal Isolations

• PV input terminals: Isolated from other input/output terminals.

Not isolated from internal circuit.

• 15 V DC loop power supply terminals: Not isolated from 4-20

mA analog output. Isolated from other input/output
terminals and internal circuit.

• 24 V DC loop power supply terminals: Isolated from 4-20 mA

analog output terminals, other input/output terminals and
internal circuit.

• 4-20 mA analog output terminals (for retransmission): Not

isolated from 15 V DC loop power supply. Isolated from
other input/output terminals and internal circuit.

• Contact input terminals: Not isolated from communication

terminals. Isolated from other input/output terminals and
internal circuit.

• Relay contact output terminals: Not isolated between relay

contact output terminals. Isolated from other input/output
terminals and internal circuit.

• RS-485 communication terminals: Not isolated from contact

input terminals. Isolated from other input/output terminals
and internal circuit.

• Power terminals: Isolated from other input/output terminals and

internal circuit.

• Grounding terminals: Isolated from other input/output terminals

and internal circuit.

Environmental Conditions

• Normal operating conditions:

Ambient temperature: 0 to 50

C (40

C or less for side-by-side

close installation)
0 to 40

C if the 24V DC loop power supply of Model

UM330 is used

Temperature change rate: 10

C/h or less

Ambient humidity: 20 to 90% RH (no condensation allowed)
Magnetic field: 400 A/m or less
Continuous vibration at 5 to 14 Hz: Full amplitude of 1.2 mm or

less

Continuous vibration at 14 to 150 Hz: 4.9 m/s

2

 or less

Short-period vibration: 14.7 m/s

2

, 15 seconds or less

Shock: 147 m/s

2

 or less, 11 ms

Installation height: Height above sea level of 2000 m or less
Warm-up time: 30 minutes or more after power on

• Transportation and storage conditions:

Temperature: -25 to 70

C

Temperature change rate: 20

C/h or less

Humidity: 5 to 95% RH (no condensation allowed)

• Effects of changes in operating conditions

- Effects from changes in ambient temperature:

- On voltage or thermocouple input, 

 

V/

C or 

0.01%

of F.S./

C, whichever is larger

- On RTD input, 

0.05

C /

C (ambient temperature) or less

- On analog output, 

0.05% of F.S./

C or less

- Effects from power supply fluctuation (within rated voltage

range)

- On analog input, 

 

 

V/10 V or 

 

0.01% of F.S. /10 V,

whichever is larger

- On analog output, 

0.05% of F.S./ 10 V or less

5. Hardware Specifications

PV Input Signals

• Number of inputs: 1 (terminals 

11

-

12

-

13

)

• Input type: Universal input system. The input type can be

selected with the software.

• Sampling period: 250 ms
• Burnout detection: Functions at TC, RTD, standard signal

(0.4 to 2 V or 1 to 5 V)
Upscale, downscale, and off can be specified.
For standard signal, burnout is determined to have occurred
if it is 0.1 V or less.

• Input bias current: 0.05 

 

A (for TC or RTD b-terminal)

• Measurement current (RTD): About 0.13 mA
• Input resistance: 1 M

 or more for thermocouple or mV input

About 1 M

 for DC voltage input

• Allowable signal source resistance: 250 

 or less for

thermocouple or mV input
Effects of signal source resistance: 0.1 

 

V/

 or less

2 k

 or less for DC voltage input

Effects of signal source resistance: About 0.01%/100 

• Allowable wiring resistance: for RTD input

Maximum 150 

/wire: Conductor resistance between three

wires should be equal
However, 10 

/wire for a maximum range of -150.0 to

150.0

C.

Wire resistance effect: 

0.1

C /10 

• Allowable input voltage: 

10 V DC for thermocouple, mV, or

RTD input

20 V DC for DC voltage input

• Noise rejection ratio: 40 dB (50/60 Hz or more in normal mode

120 dB (50/60 Hz) or more in common mode

• Reference junction compensation error: 

1.0

C (15 to 35

C)

1.5

C (0 to 15

C, 35 to 50

C)

• Applicable standards: JIS, IEC, DIN (ITS-90) for thermocouples

and RTD

Loop Power Supply

Power is supplied to a two-wire transmitter.

(15 V DC: terminals 

14

-

15

; 24 V DC: terminals 

21

-

22

)

A resistor (10 to 250 

) connected between the indicator

and transmitter converts a current signal into a voltage
signal, which is then read via the PV input terminal .
Supply voltage: 14.5 to 18.0 V DC, max. 21 mA (provided
with a protection circuit against a field short-circuit); 21.6
to 28.0 V DC, max. 30 mA (only for models with 24 V DC
loop power supply)

Retransmission Output

Outputs the PV value.
Either the retransmission output or the 15 VDC loop power

supply can be used with terminals 

16

-

17

.

• Number of outputs: 1 (terminals 

16

-

17

)

• Output signal: 4-20 mA DC
• Load resistance: 600 

 or less

• Output accuracy: 

0.3% of span under standard operating

conditions (23 

2

C, 55 

10% RH, power frequency of

50/60 Hz)

Contact Inputs

• Purpose: Resetting of PV peak and bottom values
• Number of inputs: 1

Input type: Non-voltage contact or transistor open collector input

• Input contact rating: 12 V DC, 10 mA or more
• On/off determination: For non-voltage contact input, contact

resistance of 1 k

 or less is determined as “on” and contact

resistance of 20 k

 or more as “off.”

For transistor open collector input, input voltage of 2 V or
less is determined as “on” and leakage current must not
exceed 100 

 

A when “off.”

• Minimum status detection hold time: About 1 second

Contact Outputs

• Purpose: Alarm output, FAIL output, and others
• Number of outputs: 4 (Max).
• Relay contact rating for Alarm 1 to 3: 240 V AC, 1 A, or 30 V

DC, 1 A ; 1a (FAIL output ; 1b)

• Relay contact rating for Alarm 4: 250 V AC, 3 A, or 30 V DC, 3

A (resistance load)  3 terminals (NC, NO, Common); 1c

Display Specifications

• PV display:

4-digit, 7-segment red LED display, character height of
20 mm

• Setpoint display: 4-digit, 7-segment, red LEDs, character height

of 9.3 mm

• Status indicating lamps: LEDs

Safety and EMC Standards

• Safety: Complies with IEC/EN61010-1 (CE), approved by

C22.2 No.61010-1, approved by UL508.
Installation category : CAT. II  Pollution degree : 2 (IEC/
EN61010-1, C22.2 No.61010-1)
Measurement category : I (CAT. I : IEC/EN61010-1)
Rated measurement input voltage : 10V DC max.(across
terminals), 300V AC max.(across ground)
Rated transient overvoltage : 1500V (Note)
Note : It is a value on the safety standard which is assumed
by IEC/EN61010-1 in Measurement category I, and is not
the value which guarantees an apparatus performance.

CAUTION

This equipment has Measurement category I, there-
fore do not use the equipment for measurements
within  Measurement categories II, III and IV.

1

2

3

4

Measurement category

CAT.

1

CAT.

2

CAT.

3

CAT.

4

Description

For measurements performed 
on circuits not directly 
connected to MAINS.
For measurements performed 
on circuits directly connected 
to the low voltage installation.
For measurements performed 
in the building installation.
For measurements performed 
at the source of the low-voltage 
installation.

           Remarks

Appliances, portable 
equipments, etc.

Distribution board, 
circuit breaker, etc.
Overhead wire, cable 
systems, etc.

Internal Wiring

Outlet

Entrance
Cable

4

3

1

T

2

• EMC standards: Complies with EN61326, EN61000-3-2,

EN61000-3-3 and EN55011 (CE).
Class A Group 1.
The instrument continues to operate at a measuring accuracy of
within 

20% of the range during tests.

150mm

150mm

150mm

150mm

Front panel

 of indicator

Must not 
exceed 30

30

Rear of 
indicator

Large bracket 

(top mounting hardware) 

Terminal board 

Small bracket

(bottom mounting hardware) 

Panel 

Insert a screwdriver into the
brackets to tighten the screws. 

Direction to insert the 
indicator 

Insert the indicator 
into the opening at 
the front of the panel. 

Recommended 
tightening torque
:0.4 N•m

User’s
Manual

IM 05F01D02-01E

Models UM350 / UM330
Digital Indicator with Alarms
User’s Manual

   Installation

4th Edition: Jan 31, 2005

How to Install

CAUTION

Turn off the power to the indicator before installing it on the panel because there is a possibility of electric shock.

Fold the cover in the direction 
of the arrow.

Fit the cover hold 
over the protrusion 
on the mounting bracket.

Figure A

Figure B

1. Before attaching the terminal cover, bend the side with

the groove inward as shown in Fig. A. Be careful not to
bend it backwards. This not only makes it harder to
attach the cover but will also weaken its hold.

2. Fit the holes on the top and bottom (or left and right) of

the terminal cover over the projections on the brackets
(Fig. B) and lock in place. The figure right shows the
attachment of a terminal cover to UM indicator.

Note:Right and left mounting for UM330.