Matching the control unit to the heating system
Note
The control unit must be matched to the system equipment. Various system
components are automatically recognised by the control unit, and codes are
automatically set.
&
For selection of an appropriate design, see the following diagrams.
&
For coding steps, see page 38.
System design 1
With/without DHW heating with 1 heating circuit without mixer
!
Outside temperature sensor (only
for weather-compensated control
units)
or
lH
Vitotrol 100 (only for constant
temperature control units)
%
Cylinder temperature sensor
sÖ
Heating circuit pump
sA
Cylinder loading pump (connec-
tion via external extension H1)
sK
Cylinder loading pump (connec-
tion via internal extension H1 or
H2)
A
Internal extension H1 or H2
or
External extension H1
Further details regarding the individual steps
(cont.)
24
Initial start-up, inspection, maintenance
56
92
550
GB
Содержание VITODENS 300 WB3A
Страница 10: ...Opening the control unit housing 10 5862 570 GB...
Страница 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Страница 122: ...Temperature profile Factory set code F1 6 to F1 15 Control functions cont 106 Function description 5692 550 GB...
Страница 125: ...A1 Main PCB A2 Mains supply unit Connection and wiring diagrams external connections 109 Designs 5692 550 GB...
Страница 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Страница 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Страница 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Страница 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Страница 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Страница 145: ...129 5692 550 GB...
Страница 146: ...130 5692 550 GB...
Страница 147: ...131 5692 550 GB...