Coding in
the as
delivered
condition
Address:
value
Function mode
Coding
change
Address:
value
Possible change
A2:2
With DHW cylinder
priority applicable to
heating circuit pump
and mixer
A2:0
Without DHW cylinder
priority applicable to
heating circuit pump and
mixer
A2:1
With DHW priority applic-
able to mixer: The mixer
is closed whilst DHW is
loaded; the heating cir-
cuit pump operates
*
1
A2:3
to
A2:15
Reduced priority appl. to
mixer; i.e. the heating cir-
cuit receives a reduced
amount of energy
*
1
A3:2
*
2
Outside temperature
below 1 °C: Heating cir-
cuit pump ON
Outside temperature
above 3 °C: Heating cir-
cuit pump OFF
Note
When selecting a value
below 1 °C there will be
a risk of pipes outside
the thermal insulation
envelope of the house
freezing-up. The
standby mode, in parti-
cular, should be
observed, e.g. during
holidays.
A3:-9
to
A3:15
Heating circuit pump ON/
OFF (see the following
table)
Code 2
(cont.)
53
Coding
56
92
550
GB
*1
Only adjustable for mixer circuit M2.
*2
Only for weather-compensated control units.
Содержание VITODENS 300 WB3A
Страница 10: ...Opening the control unit housing 10 5862 570 GB...
Страница 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Страница 122: ...Temperature profile Factory set code F1 6 to F1 15 Control functions cont 106 Function description 5692 550 GB...
Страница 125: ...A1 Main PCB A2 Mains supply unit Connection and wiring diagrams external connections 109 Designs 5692 550 GB...
Страница 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Страница 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Страница 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Страница 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Страница 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Страница 145: ...129 5692 550 GB...
Страница 146: ...130 5692 550 GB...
Страница 147: ...131 5692 550 GB...