Coding in
the as
delivered
condition
Address:
value
Function mode
Coding
change
Address:
value
Possible change
A5:5
*
1
With heating circuit
pump logic function
(economy circuit): Heat-
ing circuit pump OFF, if
the outside temperature
(AT) is 1 K higher than
the set room tempera-
ture (RT
Set
)
AT > RT
Set
+1 K
A5:0
Without heating circuit
pump logic function
A5:1
to
A5:15
With heating circuit pump
logic function: Heating
circuit pump OFF, if (see
the following table)
Parameter address
A5:...
With heating circuit pump logic function: Heating
circuit pump OFF, if
1
AT > RT
Set
+5 K
2
AT > RT
Set
+4 K
3
AT > RT
Set
+3 K
4
AT > RT
Set
+2 K
5
AT > RT
Set
+1 K
6
AT > RT
Set
7
to
AT > RT
Set
-1 K
15
AT > RT
Set
- 9 K
Code 2
(cont.)
55
Coding
56
92
550
GB
*1
Only for weather-compensated control units.
Содержание VITODENS 300 WB3A
Страница 10: ...Opening the control unit housing 10 5862 570 GB...
Страница 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Страница 122: ...Temperature profile Factory set code F1 6 to F1 15 Control functions cont 106 Function description 5692 550 GB...
Страница 125: ...A1 Main PCB A2 Mains supply unit Connection and wiring diagrams external connections 109 Designs 5692 550 GB...
Страница 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Страница 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Страница 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Страница 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Страница 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Страница 145: ...129 5692 550 GB...
Страница 146: ...130 5692 550 GB...
Страница 147: ...131 5692 550 GB...