57
Coding in the delivered condition
Possible change
b2:8
With remote control and
for the heating circuit,
operation with room tem-
perature hook-up must be
programmed: Room influ-
ence factor 8
(only for weather-com-
pensated control units;
change the coding only
for the heating circuit with
mixer M2)
b2:0
Without room influence
b2:1
to
b2:64
Room influence factor
adjustable from 1 to 64
b5:0
With remote control: No
room temperature-com-
pensated heating circuit
pump logic function (only
for weather-compensa-
ted control units; change
the coding only for the
heating circuit with mixer
M2)
b5:1
to
b5:8
Heating circuit pump logic
function; see the following
table
Parameter
address b5:...
With heating circuit pump logic function: Heating circuit
pump OFF, if
1:
enabled RT
actual
>
RT
set
+ 5 K; disabled RT
actual
< RT
set
+ 4 K
2:
enabled RT
actual
>
RT
set
+ 4 K; disabled RT
actual
< RT
set
+ 3 K
3:
enabled RT
actual
>
RT
set
+ 3 K; disabled RT
actual
< RT
set
+ 2 K
4:
enabled RT
actual
>
RT
set
+ 2 K; disabled RT
actual
< RT
set
+ 1 K
5:
enabled RT
actual
>
RT
set
+ 1 K; disabled RT
actual
< RT
set
6:
enabled RT
actual
>
RT
set
; disabled RT
actual
< RT
set
- 1 K
7:
enabled RT
actual
>
RT
set
- 1 K; disabled RT
actual
< RT
set
- 2 K
8:
enabled RT
actual
>
RT
set
- 2 K; disabled RT
actual
< RT
set
- 3 K
Coding in the delivered condition
Possible change
Boiler circuit, mixer circuit
C5:20
Electronic minimum flow
temperature limit 20
°
C
(only for weather-com-
pensated control units)
C5:1
to
C5:127
Minimum temperature limit
adjustable from 1 to 127
°
C
(limited by the boiler coding
card)
Codes
Code 2
(cont.)
5692 760 GB