35
Single boiler system with
Vitotronic 200-H and Vitocom 300
Set up the LON subscriber numbers and
further functions via code 2 (see the fol-
lowing table).
Note
In the same LON system, the same num-
ber cannot be allocated twice.
Only one Vitotronic may be program-
med as fault manager.
Boiler control unit
Vitotronic 200-H
Vitotronic 200-H
Vitocom
LON
LON
LON
Subscriber no. 1
Code "77:1"
Subscriber no. 10
Code "77:10"
Subscriber no. 11
Set
code "77:11"
Subscriber no.
99
Control unit is fault
manager
Code "79:1"
Control unit is not
fault manager
Code "79:0"
Control unit is not
fault manager
Code "79:0"
Device is fault
manager
Control unit transmits
the time
Code "7b:1"
Control unit receives
the time
Set
code "81:3"
Control unit receives
the time
Set
code "81:3"
Device
receives the
time
Control unit transmits
outside temperature
Set
code "97:2"
Control unit receives
outside temperature
Set
code "97:1"
Control unit receives
outside temperature
Set
code "97:1"
—
LON subscriber fault
monitoring
Code "9C:20"
LON subscriber fault
monitoring
Code "9C:20"
LON subscriber fault
monitoring
Code "9C:20"
—
Updating the LON subscriber list
Only possible if all subscribers are con-
nected and the control unit is program-
med to be fault manager (code "79:1").
Press the following keys:
1.
L
+
d
simultaneously for approx.
2 s.
Subscriber check initiated
(see page 36).
2.
e
The subscriber list is upda-
ted after approx. 2 min.
The subscriber check is
completed.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)