54
Parameters
Heating circuit pump
Address A3:...
"ON" at
"OFF" at
-6
-7
°
C
-5
°
C
-5
-6
°
C
-4
°
C
-4
-5
°
C
-3
°
C
-3
-4
°
C
-2
°
C
-2
-3
°
C
-1
°
C
-1
-2
°
C
0
°
C
0
-1
°
C
1
°
C
1
0
°
C
2
°
C
2
to
1
°
C
to
3
°
C
to
15
14
°
C
16
°
C
Coding in the delivered condition
Possible change
Boiler circuit, mixer circuit
A4:0
With frost protection (only
for weather-compensa-
ted control units)
A4:1
No frost protection, adjust-
ment only possible if cod-
ing address "A3: -9" has
been selected.
Note
Observe the note for code
"A3"
A5:5
With heating circuit pump
logic function (economy
circuit): Heating circuit
pump "OFF" if the outside
temperature (AT) is 1 K
higher than the set room
temperature (RT
set
)
AT
>
RT
set
+ 1 K (only for
weather-compensated
control units)
A5:0
Without heating circuit
pump logic function
A5:1
to
A5:15
With heating circuit pump
logic function: Heating cir-
cuit pump "OFF", if (see the
following table)
Parameter address
A5:...
With heating circuit pump logic function: Heating cir-
cuit pump OFF, if
1
AT
>
RT
set
+ 5 K
2
AT
>
RT
set
+ 4 K
3
AT
>
RT
set
+ 3 K
Codes
Code 2
(cont.)
5692 760 GB