26
6.
Adjust the upper output.
Constant temperature control unit:
a
press:
"
2
" is shown.
Weather-compensated control
unit:
a
press:
"
Full load
" is shown.
7.
Check the CO
2
content. Should the
actual value deviate from the above
ranges by more than 1 %, implement
steps from page 25.
8.
After testing, press
d
.
9.
Enter actual values into the service
report.
Matching the control unit to the heating system
The control unit must be matched to the equipment level of the system. Various sys-
tem components are recognised automatically by the control unit and the relevant
codes are adjusted automatically.
■ For the selection of an appropriate design, see the following diagrams.
■ For coding steps, see page 38.
System version 1
One heating circuit without mixer A1 (with/without DHW heating)
1
2
7
3
4
6
5
1
Vitodens 200-W
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5692 760 GB