39
Overview
Coding
Coding in the delivered condition
Possible change
System design
00 :1
System version 1:
1 heating circuit without
mixer A1, without DHW
heating
00 :2
System version 1:
1 heating circuit without
mixer A1, with DHW heat-
ing
00 :3
System version 2, 4, 5:
1 heating circuit with mixer
M2, without DHW heating
00 :4
System version 2, 4, 5:
1 heating circuit with mixer
M2, with DHW heating
00 :5
System version 3:
1 heating circuit without
mixer A1 and 1 heating cir-
cuit with mixer M2, without
DHW heating
00 :6
System version 3:
1 heating circuit without
mixer A1; 1 heating circuit
with mixer M2, with DHW
heating
Single and multi-boiler system
01:1
Single boiler system (only
for constant temperature
control units)
01:2
Multi-boiler system with
Vitotronic 300-K
Max. boiler water temp.
06:...
Maximum boiler water
temperature limit (defaul-
ted by the boiler coding
card)
06:20
to
06:127
Maximum limit of the boiler
water temperature within
the ranges defaulted by the
boiler
Venting/filling
2F:0
Venting program/fill pro-
gram disabled
2F:1
Venting program enabled
2F:2
Fill program enabled
Codes
Code 1
(cont.)
5692 760 GB