56
Coding in the delivered condition
Possible change
A8:1
Heating circuit with mixer
M2 creates a demand for
the circulation pump in
the heating circuit con-
nection set (only for
weather-compensated
control units)
A8:0
Heating circuit with mixer
M2 creates no demand for
the circulation pump in the
heating circuit connection
set
A9:7
With pump idle time:
Heating circuit pump
"OFF" if the set value
changes through a
change in operating
mode or through a
change in the set room
temperature (only for
weather-compensated
control units)
A9:0
Without pump idle time
A9:1
to
A9:15
With pump idle time;
adjustable from 1 to 15
b0:0
With remote control:
Heating mode/reduced
mode: weather-compen-
sated (only for weather-
compensated control
units; change the coding
only for the heating circuit
with mixer M2)
b0:1
Heating mode: weather-
compensated
Reduced mode: with room
temperature hook-up
b0:2
Heating mode: with room
temperature hook-up
Reduced mode: weather-
compensated
b0:3
Heating mode/reduced
mode: with room tempera-
ture hook-up
Codes
Code 2
(cont.)
5692 760 GB