21
Checking the burner gauze assembly & replacing, if required
C
B
3x
E
F
D
4x
A
1.
Remove electrodes
A
.
2.
Undo three retaining clips
B
at ther-
mal insulation ring
C
and remove
thermal insulation ring
C
.
3.
Release four Torx screws
D
and
remove burner gauze assembly
E
.
4.
Remove old burner gauze assembly
gasket
F
.
5.
Insert a new burner gauze assembly
with a new gasket and secure with
four Torx screws.
Note
Torque: 4.5 Nm
6.
Refit the thermal insulation ring
C
and electrodes
A
.
Commissioning, inspection, maintenance