15
BW 2180 1240 kg
BW 2250 1360 kg
Total weight type WW 1125 to
WW 2300
"Vitocal 300-W Pro installation
and service instructions, supple-
ments".
■ To prevent the transmission of struc-
ture-borne noise, never site the appli-
ance on ceilings with wooden joists
(e.g. in the attic).
■ Level the appliance.
If the adjustable feet are used to com-
pensate for an uneven floor (max.
10 mm), the pressure load on the feet
must be distributed evenly.
■ Observe minimum room volume (to
DIN EN 378).
Note
Additional country-specific regulations
also apply.
Min. room volume, type BW 190 to
BW 2250:
BW 190
54 m
3
BW 1120 68 m
3
BW 2150 86 m
3
BW 2180 103 m
3
BW 2250 141 m
3
Min. room volume
type WW 1125 to WW 2300
"Vitocal 300-W Pro installation
and service instructions, sup-
plements".
■ Observe the required floor area and
minimum clearances (see the follow-
ing chapter).
Minimum clearances
E
>250
>600
1500
A
C
B
D
E
>250
>500
1000
1000
B
A
C
D
D
A
Clearance depends on on-site
installation and location.
B
Observe clearances required for
installation and maintenance.
C
Cable entries.
On-site strain relief clamps required
(wall clearance ≥ 80 mm).
Preparing for installation
Installation
(cont.)
5772 458 GB
Installation