97
G
Lag heat pump 2
Connection at contact for "External
demand "
H
Zero volt contact "External demand
"
K
Lag heat pump 3
L
Central fault message input, lag
heat pump
N/C contact X3.10 / X3.11 triggers a
message.
Power supply
Isolators for non-earthed conductors
■ The main isolator (if installed) must
simultaneously isolate all non-earthed
conductors from the mains with a min-
imum contact separation of 3 mm.
■ In addition, we recommend the instal-
lation of an AC/DC-sensitive RCD
(RCD class B
) for DC (fault)
currents that can occur with energy
efficient equipment.
■ If
no
main isolator is installed, all non-
earthed cables must be isolated from
the mains by the upstream circuit
breaker with at least 3 mm contact
separation.
Danger
Incorrectly executed electrical
installations can lead to injury
from electrical current and result
in equipment damage.
Make the power supply connec-
tion and implement all earthing
measures (e.g. RCD circuit) in
accordance with the following
regulations:
■ IEC 60364-4-41
■ VDE requirements
■ Technical connection require-
ments specified by your local
power supply utility
■ Protect the power supply to the
heat pump control unit with
max. 16 A
Danger
The absence of component
earthing in the system can lead to
serious injury from electrical cur-
rent if an electrical fault occurs.
The appliance and pipework
must be connected to the equi-
potential bonding of the house in
question.
Installation sequence
Electrical connections in the heat pump control…
(cont.)
5692 875 GB
Installation
Содержание Vitocal 300 AWO-M-AC 301.A
Страница 5: ...5 Certificates Declaration of conformity 148 Keyword index 149 Index Index cont 5692 875 GB...
Страница 47: ...47 Installation sequence Removing the transport brackets cont 5692 875 GB Installation...
Страница 49: ...49 3x 9x 3 3x 3x 2 3 4 1 Installation sequence Fitting the outer panels cont 5692 875 GB Installation...
Страница 52: ...52 3x 3x 3x 3x 9 8 Installation sequence Fitting the outer panels cont 5692 875 GB...
Страница 53: ...53 3x 10 3x 2x 11 Installation sequence Fitting the outer panels cont 5692 875 GB Installation...
Страница 57: ...57 Type AWCI M AC 301 A 1 Installation sequence Siting the heat pump cont 5692 875 GB Installation...
Страница 58: ...58 Type AWO M AC 301 A 2 3 4 5 4x 1 Installation sequence Siting the heat pump cont 5692 875 GB...
Страница 104: ...104 Fitting the front panel 1 2 2 Installation sequence Closing the heat pump cont 5692 875 GB...
Страница 127: ...127 022 029 032 034 033 031 033 025 031 Parts lists Parts list type AWCI M AC 301 A cont 5692 875 GB Service...
Страница 128: ...128 051 052 008 066 038 063 064 Parts lists Parts list type AWCI M AC 301 A cont 5692 875 GB...
Страница 134: ...134 022 029 032 033 031 033 025 031 Parts lists Parts list type AWO M AC 301 A cont 5692 875 GB...
Страница 135: ...135 051 052 008 065 038 063 064 Parts lists Parts list type AWO M AC 301 A cont 5692 875 GB Service...