92
Terminals
Function
Explanation
X3.12
X3.13
or at exter-
nal exten-
sion H1
Signal "External demand"
(external starting of com-
pressor and pumps, mixer
in control operation or
OPEN, changeover of
operating mode of several
system components)
Requires zero volt
N/O
contact:
■ Closed: Demand
■ Open: No demand
■ Breaking capacity 230 V, 2 mA
Note
■ These or other external functions, such
as swimming pool water heating, cas-
cade or external set value default can
alternatively be connected via external
extension H1.
Installation instructions "External
extension H1"
■ If a swimming pool water heating facility
is connected to external extension H1,
no other external function can be con-
nected to external extension H1.
X3.17
X3.18
Fuse F1 6.3A (slow)
X5/X7
Control cable 230 V~
Terminals for connecting cable to the con-
trol panel
Controller and sensor PCB
Note
■ Plug F11:
Nothing should be connected to plug
F11 on site.
■ Flow temperature sensor for heat-
ing circuit with mixer (M3):
The flow temperature sensor for one
heating circuit with mixer (M3) is con-
nected to the extension kit for heating
circuit with mixer (accessory).
Installation sequence
Electrical connections in the heat pump control…
(cont.)
5692 875 GB
Содержание Vitocal 300 AWO-M-AC 301.A
Страница 5: ...5 Certificates Declaration of conformity 148 Keyword index 149 Index Index cont 5692 875 GB...
Страница 47: ...47 Installation sequence Removing the transport brackets cont 5692 875 GB Installation...
Страница 49: ...49 3x 9x 3 3x 3x 2 3 4 1 Installation sequence Fitting the outer panels cont 5692 875 GB Installation...
Страница 52: ...52 3x 3x 3x 3x 9 8 Installation sequence Fitting the outer panels cont 5692 875 GB...
Страница 53: ...53 3x 10 3x 2x 11 Installation sequence Fitting the outer panels cont 5692 875 GB Installation...
Страница 57: ...57 Type AWCI M AC 301 A 1 Installation sequence Siting the heat pump cont 5692 875 GB Installation...
Страница 58: ...58 Type AWO M AC 301 A 2 3 4 5 4x 1 Installation sequence Siting the heat pump cont 5692 875 GB...
Страница 104: ...104 Fitting the front panel 1 2 2 Installation sequence Closing the heat pump cont 5692 875 GB...
Страница 127: ...127 022 029 032 034 033 031 033 025 031 Parts lists Parts list type AWCI M AC 301 A cont 5692 875 GB Service...
Страница 128: ...128 051 052 008 066 038 063 064 Parts lists Parts list type AWCI M AC 301 A cont 5692 875 GB...
Страница 134: ...134 022 029 032 033 031 033 025 031 Parts lists Parts list type AWO M AC 301 A cont 5692 875 GB...
Страница 135: ...135 051 052 008 065 038 063 064 Parts lists Parts list type AWO M AC 301 A cont 5692 875 GB Service...