Requirements for the contact humidistat:
■
Electrical connection, subject to the type of contact
humidistat:
–
24 V (recommended):
Connection to F11 on the controller and sensor
PCB
–
230 V~, 0.5 A:
Connection to X3.8/3.9 on the luster terminals
■
Installation inside the room to be cooled at the cool-
ing water flow (remove thermal insulation if required)
■
If several rooms with different relative humidity levels
are part of the cooling circuit, fit and connect several
contact humidistats in series:
Design the switching contacts as N/C contacts.
Removing the front panels
3.
4.
2x
2.
1.
5.
Fig. 22
Installation sequence
Type AWOT(-M)-E-AC only: Connecting the cooling circuit
(cont.)
5831412
Installation