25
Minimum room height
1904
> a
A
B
Fig. 17
A
Indoor unit
B
Finished floor level or top edge of platform for
unfinished floors
Minimum room height a depends on the hydraulic con-
nection set used.
Hydraulic connection set
Minimum
room height a
in mm
■
For installation on finished walls, for
upward connection
2200
■
For installation to the left or right on
finished walls
2000
Note
If applicable, remove the packaging box upwards
before installation.
Pressure points
b
Ø d
c
a
Fig. 18
A
Partition joint with edge insulation strip as part of
the floor construction
a
439 mm
b
506 mm
c
670 mm
d
64 mm
Note
■
Observe the permissible floor load.
■
Level the appliance horizontally.
■
If the adjustable feet are used to compensate for an
uneven floor (max. 10 mm), distribute the pressure
load on the individual feet evenly.
The total weight with filled DHW cylinder is 384 kg.
Each pressure point (each with an area of 3217 mm
2
)
is subject to a load of up to 96 kg.
Installation sequence
Installing the indoor unit
(cont.)
5831412
Installation
Содержание Vitocal 222-A
Страница 80: ...80 Fig 64 Maintenance Indoor unit Placing the control unit panel in its service position 5831412 Maintenance...
Страница 92: ...92 Maintenance Checking the fuses cont 5831412 Maintenance...
Страница 102: ...102 0004 0005 0001 0002 0003 0006 0007 Fig 74 Indoor unit parts lists Miscellaneous 5831412 Components...
Страница 104: ...104 Indoor unit parts lists Miscellaneous cont 5831412 Components...
Страница 112: ...112 Outdoor unit parts list 230 V types 221 A04 to A08 Outdoor unit electrical equipment 230 V cont 5831412 Components...
Страница 120: ...120 Outdoor unit parts list 230 V types 221 A10 to A16 Outdoor unit electrical equipment 230 V cont 5831412 Components...
Страница 154: ...154 5831412...
Страница 155: ...155 5831412...