Requirements for the installation room
!
Please note
Unfavourable ambient conditions can lead to
malfunctions and appliance damage.
■
The installation room must be dry and free
from the risk of frost.
■
Ensure ambient temperatures between 0 and
35 °C.
■
Max. 70 % relative humidity (corresponds to
an absolute humidity of approx. 25 g water
vapour/kg dry air)
Danger
Dust, gases and vapours can be damaging to
health and trigger explosions.
Avoid dust, gases and vapours in the installation
room.
!
Please note
Overloading the floor can result in damage to
the building structure.
Observe the permissible floor load. Take
account of the total weight of the appliance: See
chapter "Pressure points".
Minimum clearances
Secondary circuit connections, left/top
1000
250
Fig. 15
Secondary circuit connections, right/top
1000
250
Fig. 16
Installation sequence
Installing the indoor unit
(cont.)
5831412
Installation
Содержание Vitocal 222-A
Страница 80: ...80 Fig 64 Maintenance Indoor unit Placing the control unit panel in its service position 5831412 Maintenance...
Страница 92: ...92 Maintenance Checking the fuses cont 5831412 Maintenance...
Страница 102: ...102 0004 0005 0001 0002 0003 0006 0007 Fig 74 Indoor unit parts lists Miscellaneous 5831412 Components...
Страница 104: ...104 Indoor unit parts lists Miscellaneous cont 5831412 Components...
Страница 112: ...112 Outdoor unit parts list 230 V types 221 A04 to A08 Outdoor unit electrical equipment 230 V cont 5831412 Components...
Страница 120: ...120 Outdoor unit parts list 230 V types 221 A10 to A16 Outdoor unit electrical equipment 230 V cont 5831412 Components...
Страница 154: ...154 5831412...
Страница 155: ...155 5831412...