125
Heating circuit 1
Parameter
Code
Delivered condi-
tion
Commis-
sioning
"Standard room temperature"
2000
200 (
≙
20 °C)
"Reduced room temperature"
2001
160 (
≙
16 °C)
"Remote control"
2003
0
"Heating curve level"
2006
0 (
≙
0 K)
"Heating curve slope"
2007
6 (
≙
0.6)
"Influence room temperature hook-
up"
200A
10
"Room temperature hook-up"
200B
0
"Max. flow temperature heating cir-
cuit"
200E
400 (
≙
40 °C)
"Room temperature in party mode"
2022
200 (
≙
20 °C)
Heating circuit 2
Parameter
Code
Delivered condi-
tion
Commis-
sioning
"Standard room temperature"
3000
200 (
≙
20 °C)
"Reduced room temperature"
3001
160 (
≙
16 °C)
"Remote control"
3003
0
"Heating curve level"
3006
0 (
≙
0 K)
"Heating curve slope"
3007
6 (
≙
0.6)
"Influence room temperature hook-
up"
300A
10
"Room temperature hook-up"
300B
0
"Max. flow temperature heating cir-
cuit"
300E
400 (
≙
40 °C)
"Room temperature in party mode"
3022
200 (
≙
20 °C)
Cooling
Parameter
Code
Delivered condi-
tion
Commis-
sioning
"Cooling function"
7100
0
"Cooling circuit"
7101
1
"Set room temperature separate cool-
ing circuit"
7102
200 (
≙
20 °C)
"Min. flow temperature cooling"
7103
100 (
≙
10 °C)
Commissioning/service reports
Control parameters report
(cont.)
5782 176 GB