134
Type AWB/AWB-AC
201.C10
201.C13
Air intake temperature
(type AWB-AC)
Cooling mode
■ Min.
°C
15
15
■ Max.
°C
45
45
Heating mode
■ Min.
°C
–20
–20
■ Max.
°C
35
35
Heating water
at 10 K spread
Capacity (excl. expansion vessel)
l
3.2
3.2
Minimum flow rate (always maintain)
l/h
1200
1380
Max. external pressure drop (RFH) at min.
flow rate
mbar
kPa
440
44
380
38
Max. flow temperature
°C
55
55
External unit electrical values
■ Rated voltage, compressor
3/N/PE 400 V/50 Hz
■ Max. rated current, compressor
A
16
16
■ Starting current, compressor
A
10
10
■ Starting current, compressor with stalled
armature
A
16
16
■ Starting current (charging DC capacitors) A
30
30
■ Fuse protection
A
20
20
■ IP rating
IP
24
24
Internal unit electrical values
Heat pump control unit/PCB
■ Rated voltage, control unit/PCB
1/N/PE 230 V/50 Hz
■ Fuse protection, power supply
1 x B 16 A
■ Internal fuse
6.3 A (slow)/250 V
Instantaneous heating water heater
Only for type AWB-AC
■ Rated voltage
1/N/PE 230 V/50 Hz
3/N/PE 400 V/50 Hz
■ Heating output
kW
8.8
8.8
■ Fuse protection, power supply
3 x B 16 A
3 x B 16 A
Electrical power consumption
■ Fan (max.)
W
130
130
■ External unit (max.)
kW
5.8
5.8
■ Secondary pump (PWM)
W
3 – 70
3 – 70
■ Control unit/PCB, external unit (max.)
W
150
150
■ Control unit/PCB, internal unit (max.)
W
5
5
■ Max. rating, control unit/PCB
W
1000
1000
Specification
Specification
(cont.)
5782 176 GB
Содержание Vitocal 200-S
Страница 80: ...80 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5782 176 GB...
Страница 81: ...81 Placing the control panel in its service position 4x 1 3 2 Troubleshooting Repairs cont 5782 176 GB Service...
Страница 145: ...145 5782 176 GB...
Страница 146: ...146 5782 176 GB...
Страница 147: ...147 5782 176 GB...