122
System definition
Parameter
Code
Delivered condi-
tion
Commis-
sioning
"System scheme"
(see chapter "System
scheme")
7000
2
"Temperature differential for calculat-
ing the heating limit"
7003
40 (
≙
4 K)
"Temperature differential for calculat-
ing the cooling limit"
7004
40 (
≙
4 K)
"Swimming pool"
7008
0
"External extension"
7010
0
"System components for external
changeover"
7011
0
"Operating status for external change-
over"
7012
2
"Duration of external changeover"
7013
8 h
"Effect of external demand on heat
pump/heating circuits"
7014
4
"Effect of ext. blocking on heat pump/
heating circuits"
7015
4
"Vitocom 100"
7017
0
"Effect of external blocking on pumps/
compressor"
701A
0
"Common flow temperature sensor
system"
701B
0
Compressor
Parameter
Code
Delivered condi-
tion
Commis-
sioning
"Enable compressor"
5000
1
"Enable use of compressor stage"
5012
15
"Output compressor stage"
5030
Rated heating out-
put according to
type plate
Commissioning/service reports
Control parameters report
(cont.)
5782 176 GB