123
External heat source
Parameter
Code
Delivered condi-
tion
Commis-
sioning
"Enable external heat source"
7B00
0
"Priority ext. heat source/instant. heat-
ing water heater"
7B01
1
"Dual mode temperature external heat
source"
7B02
100 (
≙
10 °C)
"Enable external heat source for DHW
heating"
7B0D
0
"Shutdown limit, heat pump dual
mode"
7B0F
–500 (
≙
–50 °C)
DHW
Parameter
Code
Delivered condi-
tion
Commis-
sioning
"Set DHW temperature"
6000
500 (
≙
50 °C)
"Min. DHW temperature"
6005
100 (
≙
10 °C)
"Max. DHW temperature"
6006
600 (
≙
60 °C)
"Hysteresis DHW temperature heat
pump"
6007
50 (
≙
5 K)
"Hysteresis DHW temperature booster
heater"
6008
100 (
≙
10 K)
"Start optimisation for DHW heating"
6009
0
"Stop optimisation for DHW heating"
600 A 0
"Set DHW temperature 2"
600C
600 (
≙
60 °C)
"Temperature sensor at bottom of
DHW cylinder"
600E
0
"Enable booster heaters for DHW heat-
ing"
6014
0
"Enable electric heaters for DHW heat-
ing"
6015
1
"Priority DHW heating with combi cyl-
inder"
6016
0
"Start attempts for DHW after high
pressure shutdown"
6017
1
"Operating mode cylinder primary
pump"
6020
Do not adjust
Commissioning/service reports
Control parameters report
(cont.)
5782 176 GB
Service