Trouble-shooting
50
Operating instructions for the natural gas-fuelled CHP module
VITOBLOC 200
6130329
GB
7.1
Fault messages from the CHP module that cannot be acknowledged
error message
fault clearance
possible cause of the fault
emergency stop
●
release emergency stop button at the
door of the module control panel with
key or release type-specific external
emergency stop as instructed
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
emergency stop button has been pressed
●
external emergency stop button (-X1/10-11)
has been pressed
●
safety temperature limiter has tripped
●
control CPU: self-monitoring has switched off
(CPU inactive)
minimum oil level
●
check lubrication oil reserves at the
inspection glass on the left front side of
the module:
-
if oil is missing, have the lubrication
oil tank re-filled;
-
in the event of an oil leakage at the
module call customer service im-
mediately.
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
floating switch of the automatic oil refill
mechanism has switched off
●
oil tank empty or refill cock closed
minimum cooling
water pressure
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
cooling water pressure switch has tripped,
pressure too low
minimum gas pres-
sure
●
establish, whether the gas supply is
interrupted
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
gas pressure switch has tripped, gas pres-
sure too low, filter dirty
safety temperature
●
call customer service
●
STB has tripped
alternator tempera-
ture
●
let the alternator cool down (1/2 hour)
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
alternator overheated
sound hood tem-
perature
●
let the module cool down (1/2 hour)
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
sound hood thermostat has tripped
faulty fan
●
call customer service
●
thermostat relay in the fan or in the fuse has
tripped
faulty cooling water
pump
●
call customer service
●
motor protecting switch for the pump has
switched off
minimum oil pres-
sure
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
engine oil pressure too low
●
oil pressure transducer defective