![Viessmann Vitobloc 200 EM-140/207 Скачать руководство пользователя страница 51](http://html.mh-extra.com/html/viessmann/vitobloc-200-em-140-207/vitobloc-200-em-140-207_operating-instructions-manual_1018078051.webp)
Trouble-shooting
VITOBLOC 200
Operating instructions for the natural gas-fuelled CHP module
51
6130329
GB
error message
fault clearance
possible cause of the fault
cooling water tem-
perature
●
let the engine cool down
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
temperature of the engine cooling water too
high, no heat reduction on site
maximum exhaust
gas temperature
●
let the exhaust gas temperature cool
down below 300 °C (display: see Fig. 3)
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
exhaust gas temperature exceeds the limit
●
spark plug defective, ignition coil defective
●
ignition cables defective, ignition trigger
defective
●
engine setting too fat
●
sensor defective
starting speed
< 50 rpm
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
starter does not engage
●
battery empty, starter defective
●
pick-up defective, cable breakage
firing speed
rpm
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
engine does not start
●
throttle does not open
●
air filter dirty
speed range
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
engine run erratically
●
speed control system defective, worn out or
incorrectly set
overspeed
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
speed control system defective, worn out or
incorrectly set
underspeed/
pick-up
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
engine stalled or pick-up defective
synchronization
faulty
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
engine speed erratic
●
mains frequency erratic
alternator undervolt-
age
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
engine speed too low
●
alternator control defective
alternator overcur-
rent
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
alternator overloaded or alternator control
defective
alternator load im-
balance
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
different phase loads or contact problems on
site
reverse power
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
gas, ignition or speed control problems,
alternator driven by the mains
faulty output regula-
tor
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
output deviation, control system defective
●
dirty exhaust gas heat exchanger and/or air
filter
faulty alternator
contactor
●
acknowledge fault with function key F8;
call customer service if error message
1)
is repeated
●
alternator contactor does not open correctly
or feedback defective