ZIGBEE PULSE GENERATOR

INSTRUCTION SHEET

BRN

WIRE HARNESS
CONNECTIONS

Pulse

Output

SOLID STATE INSTRUMENTS

A division of Brayden Automation Corp.

6230 Aviation Circle, Loveland Colorado 80538

Phone: (970)461-9600   Fax: (970)461-9605

E-mail: [email protected]

Revision: 10/8/2018

P/N: 05911-97006A

MPG-2ES

Standard Solid State

MOUNTING POSITION -

 The MPG-2ES may be mounted in any position but is intended to be mounted with the

orientation above such that the circuit board is upright.  The MPG-2ES must be mounted within 75' of the meter.
Actual operational distance may vary with building construction and ability for the RF signal to penetrate building
materials.  For best results, mount the MPG-2ES as close to the meter as reasonably possible.

POWER SUPPLY INPUT -

 The MPG-2ES is powered from +5VDC.  Connect the RED wire to the +5VDC positive

source. Connect the BLK wire to the 5VDC ground (negative) terminal.

ZIGBEE WIRELESS COMMUNICATION -

 The MPG-2ES is designed to receive power monitoring information from

an electric meter equipped with Zigbee wireless communications.  The Zigbee tranceiver dongle is mounted on the
MPG-2ES's circuit board.  Ensure that the dongle is properly seated in the USB host socket. Do not remove.

PULSE OUTPUT -

 A 2-wire (Form A) K-Y output is available for connection to the pulse receiving device.  The BLK

wire is connected to the K terminal.  The YEL wire is connected to the Y terminal.  The output load should be limited
to 100 mA at 24 VAC/VDC with maximum output power dissipation of 800mW.

Zigbee USB

Dongle

USB Host Socket

for Zigbee Dongle

USB
Programming
Port

OPERATION -

 See the following pages for a full explanation of the operation of the MPG-2ES.

YEL

RED

BLK

(GND)

(+5V)

ER

TR

DP

GENERAL -

 The MPG-2ES is a scaled-down, specific purpose version of the MPG-1C and MPG-2 that allows cost

reduction when only basic features and one K-Y output are needed.

COM LEDs

Содержание MPG-2ES

Страница 1: ...ive source Connect the BLK wire to the 5VDC ground negative terminal ZIGBEE WIRELESS COMMUNICATION The MPG 2ES is designed to receive power monitoring information from an electric meter equipped with Zigbee wireless communications The Zigbee tranceiver dongle is mounted on the MPG 2ES s circuit board Ensure that the dongle is properly seated in the USB host socket Do not remove PULSE OUTPUT A 2 wi...

Страница 2: ...ation Corp Solid State Instruments div 6230 Aviation Circle Loveland CO 80538 970 461 9600 970 461 9205 fax www solidstateinstruments com MPG 2ESWiringDiagram vsd AMI Electric Meter w Zigbee Radio K1 Y1 Pulse Output MPG 2ES Wireless Pulse Generator Relay Service Entrance To Line 1 3 2 NEU To Loads Wireless Data 75 max USB RAVEn dongle To EMS 5VDC Power Supply Connection 5VDC GND Host Port ...

Страница 3: ...ter to which the MPG 2ES will be paired 1 2 Hardware Installation Once you are confident that the MPG 2ES s Zigbee transceiver is paired with the meter completing the installation of the physical unit is the next step If the utility is doing the MPG 2ES installation and they are experienced in provisioning then the provisioning process may be done after installation Installation includes mounting ...

Страница 4: ... the network has not been created and the MPG 2ES will not receive information from the dongle If no connection has been made the MPG 2ES will reset the dongle every 120 seconds default reset time attempting to establish a connection The RED LED on the dongle MUST be lit continuously before moving on If it is not then it is not provisioned correctly with the utility s meter Do not proceed until th...

Страница 5: ...ser 4 4 Read System Parameters Stop the monitoring mode and press Read button to view the current status or value of all current system programming parameters This is what is currently stored in the MPG 2ES s memory The MPG 2ES will return the following information Multiplier 1 Pulse Value 10 Watt hours Output Mode Normal Output Form C Dongle Mode Normal Reset Time 120 seconds Filter Enabled Filte...

Страница 6: ...facilities will require a larger pulse value to keep from overranging the MPG 2ES s registers or the maximum number of output pulses per second Enter 100 in the Pulse Value field and press Send to set the Output Pulse Value at 100 wh pulse The Pulse Value on the SSI UP will now show the correct value Pulse Value 100 Watt hours 5 3 Set Output Mode For one direction operation set the MPG 2ES s Outpu...

Страница 7: ...he serial link to the MPG 2ES will return 200 5 6 Full Factory Reset If you find that you want to reset all parameters of the MPG 2ES back to the factory defaults pull down the File dropdown menu and select Reset Factory Defaults The following parameters will default back to the factory settings as follows Multiplier 1 Pulse Value 10 Reset Time 120 seconds Note that this resets the non volatile me...

Страница 8: ...ce receiving the pulses and the methodology it uses to interpret them this can be a great help in representing the real kW demand and eliminate the quantitization problem caused by the meter s measureement method To enable the filter mode select Enable in the Filter field Hit Send The serial link on the MPG 2ES will return the following Enabled To disable the filter mode select Disable in the Filt...

Страница 9: ...n that an error has occurred The operation of the MPG 2ES will continue even though some pulses were lost In this way you can quickly determine if a pulse output value is too small and thus pulses too fast at a high demand However in the optimum application pulses would not exceed more than one pulse every 2 seconds with a 1 pulse per second maximum This allows a very even and normal pulse rate th...

Страница 10: ...alternately opened and closed This mode is best for timing pulses to derive kW demand Contact the factory for technical support at 970 461 9600 In the Fixed output mode shown in Figure 2 below an output pulse K Y closure only is a fixed width T1 each time the output is triggered The pulse width closure time is determined by the Form A Pulse Width setting using the Programming port See Page 7 This ...

Страница 11: ...put Operation K Y Out Open Closed KY closure time In Signed mode with a Form A output mode selected the K Y output pulse represents positive or kWh delivered energy with a fixed width pulse Negative or kWh received energy is ignored Positive Figure 3 3 Wire FORM C TOGGLE Output Operation K Y Out Open Closed Positive Energy Pulse Outputs Only Positive and Negative Energy Pulse Outputs In Signed mod...

Страница 12: ... CR or S0 CR Set into normal mode positive only with Form A or C set by C command s1 CR or S1 CR Set into signed mode positive negative with only Form A d0 CR or D0 CR Set into dongle normal mode d1 CR or D1 CR Set into dongle echo mode z CR or Z CR Set factory defaults v CR or V CR Query firmware version Pulse Output Mode Form c0 CR or C0 CR Pulse output mode Form C disabled Form A Output Mode c1...

Отзывы: