5.4 (Con't)
In the Form A (fixed) mode, only the K-Y output is used.  This is the standard 2-Wire system where the output contact is
normally-open until such time as a pulse is generated.  When a pulse is generated, the contact is closed for a selected fixed
time interval(dwell) in milliseconds.  Form A mode is generally associated with energy measuring systems that are only
counting kWh or some other volumetric unit but are not concerned about how or at what rate the energy is consumed at.
For Form C (Toggle) Mode:
Select C and <Send> to set the Output Form field to the Toggle (Form C) Mode.  The serial link to the MPG-2ES will return:
----------------------------------------
C
----------------------------------------

For Form A (Fixed) Mode:
Select A and <Send> to set the Output Form field to the Fixed (Form A) Mode.  The serial link to the MPG-2ES will return:
----------------------------------------
A
----------------------------------------

5.5

Set the Form A Pulse Width Time

If you are using the MPG-2ES in the Fixed Mode, set the output closure time or pulse width using the Form A Width field,
selectable 25 to 1000 mS (~1 second) in 6 possible pulse widths.  Upon a pulse being generated, the K-Y terminals of each
contact will close for the selected pulse width. This setting applies only to the Form A output mode, and does not affect the
toggle output mode.  Use the Form A Width field pull-down menu to select the output pulse width to 200 mS, for example.
Press <Send>.  The serial link to the MPG-2ES will return:
----------------------------------------
200
----------------------------------------

5.6

Full Factory Reset

If you find that you want to reset all parameters of the MPG-2ES back to the factory defaults, pull down the File dropdown
menu and select 

Reset Factory Defaults

.  The following parameters will default back to the factory settings as follows:

Multiplier=1
Pulse Value: 10
Reset Time: 120 seconds

Note that this resets the non-volatile memory of the MPG-2ES's processor only.  It does not reset the memory in the dongle.
Contact factory regarding factory reset of the dongle.

5.7

Viewing the Firmware Version

The MPG-2ES's firmware version is displayed in the upper left-hand corner of the SSI-UP software and shows:

You are connected to an: MPG-2 V2.13

5.8

Dongle Monitor Mode

There are two dongle readout modes available on the MPG-2ES, 

Normal

 and 

Echo

.  The Normal mode is the default and

shows you the Time Stamp, the Demand, the Multiplier and the Divisor coming from the meter.  The Normal mode is set by
selecting the Normal radio button on the right side of the SSI-UP dialog box and clicking on 

Monitor

.

The Echo mode allows you to view the entire transmission coming from the meter the way it is received by the MPG-2ES'
microcontroller from the dongle in XML format.  This mode may be useful in troubleshooting in the event of  intermittent
transmissions from the meter.  The Echo mode is set by selecting the Echo radio button on the right side of the SSI-UP
dialog box and clicking on 

Monitor

.

MPG-2ES Wireless Meter Pulse Generator

Содержание MPG-2ES

Страница 1: ...ive source Connect the BLK wire to the 5VDC ground negative terminal ZIGBEE WIRELESS COMMUNICATION The MPG 2ES is designed to receive power monitoring information from an electric meter equipped with Zigbee wireless communications The Zigbee tranceiver dongle is mounted on the MPG 2ES s circuit board Ensure that the dongle is properly seated in the USB host socket Do not remove PULSE OUTPUT A 2 wi...

Страница 2: ...ation Corp Solid State Instruments div 6230 Aviation Circle Loveland CO 80538 970 461 9600 970 461 9205 fax www solidstateinstruments com MPG 2ESWiringDiagram vsd AMI Electric Meter w Zigbee Radio K1 Y1 Pulse Output MPG 2ES Wireless Pulse Generator Relay Service Entrance To Line 1 3 2 NEU To Loads Wireless Data 75 max USB RAVEn dongle To EMS 5VDC Power Supply Connection 5VDC GND Host Port ...

Страница 3: ...ter to which the MPG 2ES will be paired 1 2 Hardware Installation Once you are confident that the MPG 2ES s Zigbee transceiver is paired with the meter completing the installation of the physical unit is the next step If the utility is doing the MPG 2ES installation and they are experienced in provisioning then the provisioning process may be done after installation Installation includes mounting ...

Страница 4: ... the network has not been created and the MPG 2ES will not receive information from the dongle If no connection has been made the MPG 2ES will reset the dongle every 120 seconds default reset time attempting to establish a connection The RED LED on the dongle MUST be lit continuously before moving on If it is not then it is not provisioned correctly with the utility s meter Do not proceed until th...

Страница 5: ...ser 4 4 Read System Parameters Stop the monitoring mode and press Read button to view the current status or value of all current system programming parameters This is what is currently stored in the MPG 2ES s memory The MPG 2ES will return the following information Multiplier 1 Pulse Value 10 Watt hours Output Mode Normal Output Form C Dongle Mode Normal Reset Time 120 seconds Filter Enabled Filte...

Страница 6: ...facilities will require a larger pulse value to keep from overranging the MPG 2ES s registers or the maximum number of output pulses per second Enter 100 in the Pulse Value field and press Send to set the Output Pulse Value at 100 wh pulse The Pulse Value on the SSI UP will now show the correct value Pulse Value 100 Watt hours 5 3 Set Output Mode For one direction operation set the MPG 2ES s Outpu...

Страница 7: ...he serial link to the MPG 2ES will return 200 5 6 Full Factory Reset If you find that you want to reset all parameters of the MPG 2ES back to the factory defaults pull down the File dropdown menu and select Reset Factory Defaults The following parameters will default back to the factory settings as follows Multiplier 1 Pulse Value 10 Reset Time 120 seconds Note that this resets the non volatile me...

Страница 8: ...ce receiving the pulses and the methodology it uses to interpret them this can be a great help in representing the real kW demand and eliminate the quantitization problem caused by the meter s measureement method To enable the filter mode select Enable in the Filter field Hit Send The serial link on the MPG 2ES will return the following Enabled To disable the filter mode select Disable in the Filt...

Страница 9: ...n that an error has occurred The operation of the MPG 2ES will continue even though some pulses were lost In this way you can quickly determine if a pulse output value is too small and thus pulses too fast at a high demand However in the optimum application pulses would not exceed more than one pulse every 2 seconds with a 1 pulse per second maximum This allows a very even and normal pulse rate th...

Страница 10: ...alternately opened and closed This mode is best for timing pulses to derive kW demand Contact the factory for technical support at 970 461 9600 In the Fixed output mode shown in Figure 2 below an output pulse K Y closure only is a fixed width T1 each time the output is triggered The pulse width closure time is determined by the Form A Pulse Width setting using the Programming port See Page 7 This ...

Страница 11: ...put Operation K Y Out Open Closed KY closure time In Signed mode with a Form A output mode selected the K Y output pulse represents positive or kWh delivered energy with a fixed width pulse Negative or kWh received energy is ignored Positive Figure 3 3 Wire FORM C TOGGLE Output Operation K Y Out Open Closed Positive Energy Pulse Outputs Only Positive and Negative Energy Pulse Outputs In Signed mod...

Страница 12: ... CR or S0 CR Set into normal mode positive only with Form A or C set by C command s1 CR or S1 CR Set into signed mode positive negative with only Form A d0 CR or D0 CR Set into dongle normal mode d1 CR or D1 CR Set into dongle echo mode z CR or Z CR Set factory defaults v CR or V CR Query firmware version Pulse Output Mode Form c0 CR or C0 CR Pulse output mode Form C disabled Form A Output Mode c1...

Отзывы: