36
Fault code
*1
Shown on
display
System characteristics
Cause of fault
Measure
F 54
F 54
PWM values incorrect
EEPROM of memory
stick modified or deleted;
memory stick faulty
Replace memory stick.
I
Danger
Plug-in terminals on
the burner control
unit are live.
Only replace memory
stick when burner
control unit has been
isolated from power
supply.
F 55
F 55
Parameter memory stick
fault
Memory stick faulty
Replace memory stick.
I
Danger
Plug-in terminals on
the burner control
unit are live.
Only replace memory
stick when burner
control unit has been
isolated from power
supply.
Internal system faults
Internal system faults occur if a flawless program
sequence can no longer be guaranteed.
Fault code
*1
Shown on
display
System characteristics
Cause of fault
Steps to take
01, 02, 05 to
0d, 0F, 14, 15,
17, 1A to 1c,
1E, 45, 47, Ac,
b0
01, 02, 05 to
0d, 0F, 14,
15, 17, 1A to
1c, 1E, 45,
47, Ac, b0
Fault in burner control
unit area
Internal system fault and
EMC
Replace burner control
unit.
Measure against EMC:
Try connecting to another
phase
F 0E, F
F 0E, F
Fault in burner control
unit area
EEPROM or internal sys-
tem fault; EMC fault
Have your system tested
for EMC interference; re-
place the burner control
unit.
1d
1d
Fault in burner control
unit area
Processor crashed
Have your system tested
for EMC interference; re-
place the burner control
unit.
03
03
Fault in burner control
unit
Excess temperature
(
>
60
º
C)
Check ambient tempera-
ture.
*1
All fault codes are saved to the fault memory and the last 10 can be called up.
Troubleshooting
Diagnosis
(cont.)
5783 337 GB