33
Fault code
*1
Shown on
display
System characteristics
Cause of fault
Measure
F AE
F AE
Burner control unit in a
fault state
Valve 1 leaking
Replace gas train.
F AF
F AF
Burner control unit in a
fault state
Valve 2 leaking
Replace gas train.
F A0 and F A1
F A0 and
F A1
Status duration too long,
fan ramp-up
Internal fault; fan cannot
reach its set value.
Replace the burner con-
trol unit or fan.
F A2
9
Burner control unit in a
fault state
Interruption, safety chain
has been opened (strap-
ping plug
fJ
)
Check safety chain (strap-
ping plug
fJ
)
F A3
c00
No password for parame-
ter memory stick entered
within 3 min
Values in burner control
unit and parameter mem-
ory stick differ. Timeout
due to password not be-
ing entered.
Enter password.
Installation instruc-
tions for burner
components
F A4 and F A5
F A4 and
F A5
Burner control unit in a
fault state
Internal error in feedback
from gas safety valves;
output relay does not re-
spond.
Replace burner control
unit.
F A6
F A6
Ionisation flame monitor
reports external light in-
gress during start-up or
after post-purge.
Gas train is leaking. Gas
is escaping and burning
off.
Replace gas train.
F A7
F A7
No flame reported during
safety time; ionisation
flame monitor reports no
flame signal.
Ionisation electrode set
incorrectly; ionisation ca-
ble not plugged in
Adjust ionisation elec-
trode setting (see
page 19), plug in ionisa-
tion electrode.
F A7
F A7
No flame reported during
safety time; ionisation
flame monitor reports no
flame signal.
Ignition electrodes set in-
correctly
Adjust ignition electrode
setting (see page 19)
F A7
F A7
No flame reported during
safety time; ionisation
flame monitor reports no
flame signal.
Insulation body of igni-
tion electrodes cracked
Replace ignition electro-
des.
F A7
F A7
No flame reported during
safety time; ionisation
flame monitor reports no
flame signal.
Incorrect gas type selec-
ted
Adjust gas type setting
(see page 10)
F A7
F A7
No flame reported during
safety time; ionisation
flame monitor reports no
flame signal.
Gas train does not open. Check the gas train and
replace if required.
*1
All fault codes are saved to the fault memory and the last 10 can be called up.
Troubleshooting
Diagnosis
(cont.)
5783 337 GB