34
Fault code
*1
Shown on
display
System characteristics
Cause of fault
Measure
F A7
F A7
No flame reported during
safety time; ionisation
flame monitor reports no
flame signal.
I
Danger
Plug-in terminals on
the burner control
unit are live.
Check connections
"L 1", "N" and earth
conductor.
Connections "L 1" and
"N" interchanged at the
power supply terminal of
the control unit or burner
control unit.
Check core assignment
and alter if required.
F A7
F A7
No flame reported during
safety time; ionisation
flame monitor reports no
flame signal.
Combustion characteris-
tics not ideal
Adjust burner setting (see
page 12 onwards)
F A8
F A8
Flame tears off during op-
eration
Incorrect gas type selec-
ted
Adjust gas type setting
(see page 10)
F A8
F A8
Flame tears off during op-
eration
Burner gauze assembly
faulty
Check burner gauze as-
sembly; replace if dam-
aged.
F A8
F A8
Flame tears off during op-
eration
Incorrect parameter
memory stick inserted
Replace and enable pa-
rameter memory stick.
F A8
F A8
Flame tears off during op-
eration
Combustion characteris-
tics not ideal
Adjust burner setting (see
page 12 onwards)
F A9
F A9
Flame extinguishes dur-
ing stabilising time
Incorrect gas type
Set correct gas type.
F A9
F A9
Flame extinguishes dur-
ing stabilising time
Burner gauze assembly
faulty
Check burner gauze as-
sembly; replace if dam-
aged.
F A9
F A9
Flame extinguishes dur-
ing stabilising time
Incorrect parameter
memory stick inserted
Replace and enable pa-
rameter memory stick.
F A9
F A9
Flame extinguishes dur-
ing stabilising time
Combustion characteris-
tics not ideal
Adjust burner setting.
F 04
F 04
Burner control unit lock-
out
Burner control unit has
been reset more than 5
times in the last 15 min.
Wait or carry out an ex-
tended reset, i. e. hold
down the reset button for
approx. 10 s until the fault
display begins to flash,
then immediately release
the reset button.
F 11
None
Burner switches off; dis-
play only in fault memory.
Low voltage detected
Check power supply
F 12
None
Burner switches off; dis-
play only in fault memory.
Mains failure, voltage
failure detected
Check power supply
F 13
F 13
Burner control unit in a
fault state
Safety chain is live
Check safety chain (strap-
ping plug
fJ
)
F 16
None
Burner control unit in a
fault state
EMC fault
Have the system tested
for EMC interference
*1
All fault codes are saved to the fault memory and the last 10 can be called up.
Troubleshooting
Diagnosis
(cont.)
5783 337 GB
Diagnosis