Preparing the test
C
D
E
F
Fig. 5
1.
Open the gas shut-off valve.
2.
Start the burner.
3.
Press "S"
E
and "-"
D
simultaneously.
Display
C
then shows the following:
■
Status: "d" (= control stop)
■
Service: Modulation level in % ("00" = 100 % =
upper heating output, "0" = 0 % = lower heating
output)
CO
2
test at the upper heating output
C
D
E
F
Fig. 6
1.
Press "+"
F
until the service display has incre-
mented to "00" (= 100 %).
2.
Note
The CO
2
content for all natural gases must be
between 7.5 and 10.5 %.
Check the CO
2
content at the flue pipe.
Rated heating
output in kW
Permissible CO
2
content in
%
400
8.6
±
0.3
500
8.6
±
0.3
630
8.6
±
0.3
A
B
Fig. 7
3.
If the CO
2
content needs adjusting:
■
Remove cap
B
.
■
Turn setting screw
A
in small increments (3 mm
Allen key) until the CO
2
content lies within the
specified range:
–
Turning clockwise
→
CO
2
content
falls
–
Turning anti-clockwise
→
CO
2
content
rises
4.
Record the actual value in the report (on page
54).
!
Please note
The CO
2
content must always be lower in
partial load than it is in full load.
Commissioning, inspection, maintenance
Checking the CO2 content
5783 337 GB