60
G
Double-tariff meter (for special tariff
for heat pump)
Not
permissible in conjunction with
PV systems for own energy con-
sumption.
H
Bi-directional meter (for PV systems
for own energy consumption):
Energy taken from power supply
utility and energy fed into power
supply utility
K
Meter with reverse block:
For energy generated by PV sys-
tem
L
Isolator for the domestic power sup-
ply connection (distribution panel)
M
Distribution panel
N
Domestic distribution box
Closing the heat pump
!
Please note
Seal the appliance so it is sound-
proof and
diffusion-proof
.
On pipe and hose outlets, ensure
the thermal insulation is seated
correctly.
Danger
The absence of component
earthing can lead to serious injury
from electric current if an electri-
cal fault occurs.
Attach earth conductor to front
panel and side panel.
1.
Close casing door, in reverse order to
page 32.
Note
Because of the sound insulation mat,
the casing door stands out slightly
when closed.
2.
Follow steps on page 16 in reverse
order.
Fitting side cover for external unit
In reverse order to "Opening the external
unit wiring chamber" (see page 49).
Installation sequence
Power supply
(cont.)
5782 201 GB
Содержание AWT-AC 221.A04
Страница 18: ...18 10 9 11 Installation sequence Installing the internal unit cont 5782 201 GB ...
Страница 20: ...20 2x 4x 6x 4x 22 21 20 19 Installation sequence Installing the internal unit cont 5782 201 GB ...
Страница 88: ...88 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5782 201 GB ...
Страница 102: ...102 0006 0003 0005 0001 0007 0008 0002 0004 0010 0009 Parts lists internal unit Internal unit casing cont 5782 201 GB ...
Страница 155: ...155 5782 201 GB ...