32
Type AWT-AC Line
Connection
to internal
unit
Torque in Nm
221.A13
Liquid line
7
10 mm
⅝ UNF
33–42
Hot gas line
7
16 mm
⅞ UNF
63–77
221.B10
Liquid line
7
10 mm
⅝ UNF
33–42
Hot gas line
7
16 mm
⅞ UNF
63–77
221.B13
Liquid line
7
10 mm
⅝ UNF
33–42
Hot gas line
7
16 mm
⅞ UNF
63–77
Connecting the secondary circuit
Opening the casing door
1.
Installation sequence
Connecting refrigerant lines
(cont.)
5782 201 GB
Содержание AWT-AC 221.A04
Страница 18: ...18 10 9 11 Installation sequence Installing the internal unit cont 5782 201 GB ...
Страница 20: ...20 2x 4x 6x 4x 22 21 20 19 Installation sequence Installing the internal unit cont 5782 201 GB ...
Страница 88: ...88 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5782 201 GB ...
Страница 102: ...102 0006 0003 0005 0001 0007 0008 0002 0004 0010 0009 Parts lists internal unit Internal unit casing cont 5782 201 GB ...
Страница 155: ...155 5782 201 GB ...