42
4.
Thermally insulate pipes inside the
building.
5.
Connect the drain hose to the safety
valve.
Connect the drain hose with a slope
and a pipe vent to the public sewer.
Note
■ In underfloor heating circuits, install a
temperature limiter to restrict the max-
imum temperature for underfloor heat-
ing systems (see page 48)
■ Safeguard minimum flow rate, e.g.
with overflow valve (see Specification
on page 125)
Connecting a cooling circuit if required
For area cooling systems (e.g. under-
floor heating circuit, chilled ceiling), a
contact humidistat (accessory) is
required.
Requirements for the contact humidistat:
■ Electrical connection: 230 V~, 0.5 A
■ Installation inside the room to be
cooled at the cooling water flow
(remove thermal insulation if required)
■ If several rooms with different relative
humidity are part of the cooling circuit,
fit and connect several contact humidi-
stats in series:
Switching contacts as N/C contacts
Electrical connection
Routing electrical cables to the wiring chamber of the internal
unit
Danger
Damaged cable insulation can
cause injury and damage to the
appliance.
Route cables so that they cannot
touch very hot, vibrating or sharp-
edged components.
Danger
Incorrectly routed wiring can lead
to serious injury from electrical
current and result in equipment
damage.
Installation sequence
Connecting a secondary circuit
(cont.)
5604 692 GB
Содержание AWB 201.B04
Страница 88: ...88 Opening the programming unit 1 3 2 2x Troubleshooting Repairs 5604 692 GB...
Страница 89: ...89 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5604 692 GB Service...
Страница 90: ...90 Placing the control panel in its service position 4x 1 3 2 Troubleshooting Repairs cont 5604 692 GB...
Страница 100: ...100 C B D A Parts lists internal unit Overview of assemblies internal unit 5604 692 GB...
Страница 102: ...102 0001 0005 0006 0004 0002 0008 0003 0007 0008 Parts lists internal unit Casing internal unit cont 5604 692 GB...
Страница 139: ...139 5604 692 GB...