32
B
Gravel bed as condensate soak-
away
C
Concrete foundations (see technical
guide)
D
Drainage pipe DN 100 (only with
entry points below ground level)
D
Rubber mounts (supplied)
Note
We recommend letting condensate drain
away freely (without condensate drain
pipe).
Wall mounting
Installation must
only
be performed with
the bracket set suitable for wall mounting
(accessory).
Separate installation instructions
Installing the internal unit
!
Please note
Avoid damaging the appliance
during transportation.
Never
put weight on top of the
appliance.
Installation room requirements
!
Please note
The installation room must be dry
and free from the risk of frost.
Ensure ambient temperatures 0
to 35 ºC.
!
Please note
Avoid risk of explosion due to
dust, gases and vapours
in the installation room.
Minimum room volume (to
DIN EN 378):
Type AWB/AWB-
AC
Minimum room
volume in m
3
201.B04
2.7
201.B07
4.8
201.B10
6.7
201.B13
6.7
Installation sequence
Installing the external unit
(cont.)
5604 692 GB
Содержание AWB 201.B04
Страница 88: ...88 Opening the programming unit 1 3 2 2x Troubleshooting Repairs 5604 692 GB...
Страница 89: ...89 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5604 692 GB Service...
Страница 90: ...90 Placing the control panel in its service position 4x 1 3 2 Troubleshooting Repairs cont 5604 692 GB...
Страница 100: ...100 C B D A Parts lists internal unit Overview of assemblies internal unit 5604 692 GB...
Страница 102: ...102 0001 0005 0006 0004 0002 0008 0003 0007 0008 Parts lists internal unit Casing internal unit cont 5604 692 GB...
Страница 139: ...139 5604 692 GB...